    Electrical questions and answers free
    I recently installed a new bedroom circuit with 10 receptacles and hooked up a 15 amp GFCI breaker into the panel. Once I hooked up the breaker there were no receptacles working on the line. My tester indicated that the line leaving the breaker was hot, but none of the receptacles work. What is the best way to correct this? Try a regular breaker or run a circuit tracer to determine where the open line is?
    Thanks Mark
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #2

    Jun 19, 2013, 07:24 PM
    Bedroom should have an AFCI, not a GFCI. If it is hot out of the breaker, as you indicate, then the problem must be in your wiring to the outlets. Any Junction box? Replace GFCI with AFCI to meet code.
    hkstroud's Avatar
    hkstroud Posts: 11,929, Reputation: 899
    Home Improvement & Construction Expert
     
    #3

    Jun 19, 2013, 07:28 PM
    Did you install the GFCI breaker correctly? If this is a circuit for bedroom outlets only, no bath, kitchen, garage or exterior outlets, you don't need a GFCI. You do need an arcfault breaker by latest code.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Free electrical answers to questions [ 2 Answers ]

Why 8 OF GE motor management relay 469 FAIL AT THE SAME TIME WITH GOOD POWER SUPPLY FUSE ?

Electrical questions and answers free [ 4 Answers ]

Can I connect my generator directly to an outlet that is used by my electrical dryer. I was told that as long as I shut the main it would be safe. Then I would be able to use certain appliances as long as I do not exceed the output of the generator.

Electrical questions and answers free [ 1 Answers ]

I have a problem with a Hot neutral. (This line hits 4 locations with lights & outlets) When disconnecting neutral (the line in question) at the panel. It is feeding back 110! When the breaker is turned off, I have continuity in both the lines. Now I could not duplicate those results further down...

Free answers to electrical questions [ 0 Answers ]

Can I buy nmwu #4 4 conductor cable and if so where can I find reference in the canadian code book ?


View more questions Search