    Electrical
    The minimum size copper equipment grounding conductor required on a motor branch circuit with a 30 amp circuit breaker and 12 awg copper counductors is
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #2

    Dec 15, 2013, 09:59 PM
    You can read the NEC online and find the answer. Hope this is a 240 circuit, otherwise itbis way over permitted amperage.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #3

    Dec 16, 2013, 04:58 AM
    Hope this is a 240 circuit, otherwise itbis way over permitted amperage.
    The voltage has nothing to do with the amperage/wire size relationship.
    If's a motor branch circuit so #12 on a 30A is perfectly feasible.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #4

    Dec 16, 2013, 04:59 AM
    The minimum size copper equipment grounding conductor required on a motor branch circuit with a 30 amp circuit breaker and 12 awg copper counductors is
    Do your own homework. It's all in the NEC and your study guides.

    Why not tell us what you think it is and how you get it and we'll go over it?

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

What is the virginia electrical code number restricting a electrical box in a closet [ 3 Answers ]

Need to now the code in virginia by number On the placement of a circuit box in a clooset

Hy dose one electrical outlet make my ac adapter run hotter than another electrical o [ 2 Answers ]

Why dose one electrical outlet make my ac adapter run hotter than another electrical outlet? Two different AC adapters showed the same heating tendency. Multimetered both outlets the hot one runs at 122 v the other is at 120 v. I can't see that the voltage would cause the AC adapter to run...

Toro Lawn Tractor : Electrical power not getting to the electrical clutch. How fix? [ 2 Answers ]

1992 Toro Lawn Tractor with excellent mtnce: The electrical power is not getting to the electircal clutch. What is the problem and how do I fix it? Thanks

Can substandard electrical wiring installation at home produce electrical arching [ 6 Answers ]

Can substandard electrical wiring installation at home produce electrical arching? Then fire?


View more questions Search