    electric service panel ampacity limit
    What is the rule of thumb for the sum of circuit breaker ampacities that can be installed in a breaker panel? (I know that we can put more than 10 twenty amp breakers in a 200 amp panel, but don't know what the upper limit is.)
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Oct 25, 2007, 02:42 PM
    The amount and size of breakers is irrelevant. You can fill a 40 circuit panel with 20 amp breakers, or fill it with 100 amp breakers, knowing you have 200 amp capacity. The issue is the total calculated connected load, that should not exceed 80 % of the Main, which is 160 amps.

    I realize this may not make any sense, and this is not easy to explain without going through the entire Article 220 of the NEC.

    Please come back with a more specific question related to your situation.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Relocating Service Panel [ 3 Answers ]

I am changing my electrical service from overhead to underground. At the same time I am relocating it and replacing the existing rusted service panel with a new meter base, service panel (MBSP) combination. I have a couple questions: The new location is further from the home's main panel. Can I...

Electric service panel [ 5 Answers ]

Would a 60 amp electrical service panel be too big or too small for a 2800 square foot house?

Installing second service panel [ 1 Answers ]

QUESTION: I am finishing off my basement and would like to add a service panel box in the basement. I have a 200amp panel box in my garage with 11 open slots out of 32. The builder pre wired a wire from the panel to the basement. The wire has a orange shield with #10 wire. There are 4 wires (3 and...

200 AMP Service panel to 200Amp Sub Panel [ 1 Answers ]

I getting new 200Amp service to surface mount service panel. I want to run 2oo cable to bring it sub panel in my Garage which is approx 120Ft Run through ceiling. 2 Questions 1. Is there any ristriction on running a 200AMP inside house to garage ? 2. I got a dirt cheap subpanel that has...

Service panel upgrade [ 2 Answers ]

What is entailed in changing the service box from 100 amp service to 150 or 200 amp service. Can a layman do this on his own?


View more questions Search