    Electric service panel
    Would a 60 amp electrical service panel be too big or too small for a 2800 square foot house?
    Flying Blue Eagle's Avatar
    Flying Blue Eagle Posts: 2,056, Reputation: 225
    Ultra Member
     
    #2

    Oct 1, 2007, 09:11 PM
    Hello- ccorriher :: You asked if a 60 amp. Elect. Service was big enough for a 2800 sq.ft. house ? (NO)... You need to go with a 200 amp service, to be safe Your central unit would more then finish the 60 amp out::: IS this a new house or a elect. Remodle? YOU need to go with a 200 amp service and a200 amp breaker panel.. Talk to a licensed electriction.:: I hope I have helped you ,IFG I have rate my answer below, Thanks F.B.E.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #3

    Oct 2, 2007, 06:51 AM
    Minimum size residential service is 100 amps. To determine if 100 amps is sufficient, or is a larger service needed, service size calculations need to be done, according to Article 220 of the National Electric Code.
    CaptainRich's Avatar
    CaptainRich Posts: 4,492, Reputation: 537
    Cars & Trucks Expert
     
    #4

    Oct 2, 2007, 07:49 PM
    Quote Originally Posted by ccorriher
    Would a 60 amp electrical service panel be too big or too small for a 2800 square foot house?
    Far too small. The structure must be fairly old to even have something so undersized.
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #5

    Oct 3, 2007, 07:10 AM
    I believe I saw this question on a test. Doesn't hurt to ask
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #6

    Oct 3, 2007, 11:55 AM
    I think your onto something Strat... looking at the other posts by Ccorriher.

    I hope it is understood that just knowing the square foot area of a home does not size a service.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Service Panel - Access [ 7 Answers ]

Is there any way to install finish trim around the basement service panel? I'm refinishing a basement bedroom with wallboard. Along one wall are two closets with that gray service panel between them. What kind of access to the service panel is required and does anyone have any suggestions for...

200 AMP Service panel to 200Amp Sub Panel [ 1 Answers ]

I getting new 200Amp service to surface mount service panel. I want to run 2oo cable to bring it sub panel in my Garage which is approx 120Ft Run through ceiling. 2 Questions 1. Is there any ristriction on running a 200AMP inside house to garage ? 2. I got a dirt cheap subpanel that has...

Service panel upgrade [ 2 Answers ]

What is entailed in changing the service box from 100 amp service to 150 or 200 amp service. Can a layman do this on his own?

Main Service Panel needs [ 9 Answers ]

I ran across this site accidentally today and found someone who had many of the same issues I need help with. Most of my questions were answered reading the forum however I have one more, using the following information I am hoping someone can help. The existing house is apx. 2300 sq ft w/a 200...


View more questions Search