    Electric fuse
    I bought a house it has a fuse box that runs the dryer ,the fuse box sayes 30amp fuse I put 25 amp fuses in it and they keep blowing,does this make that much of a difference,Thanks
    nmwirez's Avatar
    nmwirez Posts: 453, Reputation: 20
    Full Member
     
    #2

    Mar 3, 2007, 01:10 PM
    Quote Originally Posted by gladysman
    i bought a house it has a fuse box that runs the dryer ,the fuse box sayes 30amp fuse i put 25 amp fuses in it and they keep blowing,does this make that much of a difference,THANX
    Yes. There might be something else on the 30 amp fuse also. This has to be a 120/240V on a real old house, then this is usually the case. Changing out to a modern 100 amp main would be a good thought. Generally the laterals are sized to handle that, check with the utility co.
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #3

    Mar 3, 2007, 02:09 PM
    If it has a 30 amp fuse, it should be wired up with #10 wire. It shouldn't draw over 24 amps, so 25 amp fuses would be marginal. Likely the dryer has a short. It is just a matter of opening it up and poking through the wiring looking for it.
    nmwirez's Avatar
    nmwirez Posts: 453, Reputation: 20
    Full Member
     
    #4

    Mar 3, 2007, 02:43 PM
    Quote Originally Posted by labman
    If it has a 30 amp fuse, it should be wired up with #10 wire. It shouldn't draw over 24 amps, so 25 amp fuses would be marginal. Likely the dryer has a short. It is just a matter of opening it up and poking through the wiring looking for it.
    It could also be an overloaded motor from drum misalignment or seizing. Usually if an element shorts it will open up but blow the circuit fuse immediately. If the dryer runs after replacing the fuse and blows again, then the mechanical is dragging on the motor causing a higher current draw to blow the fuse. The motor has a thermal cutoff and will shut down on its own if there is a 30 amp fuse installed. Check the units nameplate for rating to determine how many amps it usually takes. Divide watts (va) by 240 to get amps the dryer will operate at. Generally a healthy element draws around 22 amps with motor running. So labman is correct in deducing marginal fuse.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Type H Fuse? [ 10 Answers ]

Me again,was told to buy a 30 amp disconnect for air conditioning unit.purchased an eaton/cutler hammer # 1 dpf221rp.it says it accepts class h fuses.cant seem to find anyone who knows what a class h fuse is.been to ace and home depot,can anyone help?? :confused:

Electric Fuse Wire [ 3 Answers ]

Kindly let me know, which compound is used in a fuse wire used in electric circuits

Electric Force and Electric Field? [ 1 Answers ]

Hello, Can some one explain to me briefly what's the different between electric force and electric field? I am having trouble to make them clear to myself. Thanks you so much. Jack

Blown Fuse [ 1 Answers ]

A brief background before the problem occurred. This morning I was caught in a traffic jam, wherein I had to idle the car for about 15 minutes. Thereafter the driving was normal until I stopped at a traffic signal for over 145 seconds. This time I had switched off the engine. I was unable to...

Looking for a Fuse [ 1 Answers ]

Can't find this fuse anywhere. I've checked ACE Hardware, Radio Shack and several sites on the web. BUSS AGA 3A 125V This fuse is the standard 1/4'' dia and 9/16" long. Any help will be appreciated.


View more questions Search