    Does the load balance include adding an additional circuit, or is a separate issue?
    I have balanced the load when installing a new 200 Amp. In my home home, but when we turn the window A/C (115 V), the lights in the same bedroom flicks. Adding a separate circuit for the A/C will probably solve the problem. However, is it part of the balancing the load job, or is a separate issue. I have a discrepancy with my electrician.
    Thanks,
    George
    hfcarson's Avatar
    hfcarson Posts: 1,003, Reputation: 49
    Ultra Member
     
    #2

    Oct 31, 2013, 04:44 AM
    It sounds like the momentary blink of the lamps is something most of us experience. When a significant motor load starts up it will cause a very short voltage dip... this is the likely what you are seeing. Most of the time this is normal. A separate circuit is likely to reduce this "blink".
    Balancing the loads connected to a panel is a different issue although a severely unbalanced panel may aggravate the "blink" . Has an imbalance been measured? Has the main circuit breaker ever tripped?
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #3

    Oct 31, 2013, 11:25 AM
    It is nearly impossible to balance a load in a home. The usage is far to transient and erratic. At the same time, you'd have to go out of your way to imbalance it.
    What did you do to balance it?

    Dimming lights are sometimes just normal and can't be helped. Even running a dedicated line might not solve it.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #4

    Oct 31, 2013, 12:32 PM
    Balancing the load on a panelboard is basically a crap shoot, particularly on a residential panelboard.

    Basically, you try to put the same (or as close as you can come) load in amperage on each of the panelboard's phases.

    What you are describing is not a balancing issue. It is more indicative of a circuit carrying an inrush load (High amperage peak) when something starts up, as in your A/C.

    When laser printers were first coming into the residential marketplace, there were an enormous number of complaints about lights dimming every 4 seconds or so. What was happening was that the printers (usually connected to a 15 amp circuit) would have to keep the fuser hot so every 4 seconds there would be a 15 amp inrush which would cause the surrounding lights on the circuit to dim.

    If the printer had ben on a 20 amp circuit, you would never see this condition. So my suggestion is to either change the circuit to a 20 amp circuit or put the A/C unit on its own dedicated 20 amp circuit.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

I have read that a circuit can drive a 7 ampere load.how mny watts?=7A load. [ 4 Answers ]

What appliances in our home work on 7A.) how to relate the ampere to watt conversion(eg:a bulb of 15 w need how many amp of current?

Can circuit work well if we connect 12A load to 20A circuit? [ 5 Answers ]

Hello: I have several equipment which are around 12A. I just can connect them to 20A circuit. But I am not sure if circuit will trip well under overload and short circuit. I know 15A is perfect.But,I don't have 15A circuit Thanks for everybody.

Adding an additional outlet [ 4 Answers ]

I removed the receptical I was going to get power from and found 2 cables entering the box. One was a 14-2 and the other was a 14-3. Both black wires were connected to the brass screws and both white wires were on the silver screws. The red wire was pushed into the hole in the back next to the hot...

How to wire 3 separate lights to 3 separate switches in series circuit [ 1 Answers ]

I am running wire from the circuit panel to the ceiling in the kitchen, then to a switch, back to the kitchen ceiling light. I am using the same circuit to the same thing for the dining room light with a switch, and a light on my deck also with its own switch. The switch in the dining room and the...

What is steps include when load OS [ 2 Answers ]

What is steps include when load OS


View more questions Search