    Do I need to add a sub panel to my original panel?
    Dear sir; I am replacing my 1956 heater that is still functional and adding air to the house, being told by a/c heating people I need a sub panel. Have had electricians come out telling me I have 100amp panel and one guys says the main shut to shut off whole panel maybe in attic or in a wall covered up? They say it has a split panel with a 50amp that shuts half off which covers pretty much of all in the house. The circuit breakers are bulldog push matic type and there are several empty places in the panel. If you would like pictures I can send. If I counted right there are 19 breakers. From top to bottom ii position #1 & 2 are 4(1ea) 20amp Had P2020 on side. #3 & 4 50amp (1ea) cat#31150 on side. #5&6,#7&8 (1ea) 30amp cat#31230, #9&10 (1ea) 50amp cat same as other, #11 (1ea) 15amp cat # 3115,#12 (1ea)20amp cat#31120,#13(1ea)20amp, #14 (1ea)15amp,#15&16 (1ea)20amp,#17(1ea) 20amp, #18 (1ea) 15amp, #19 (1ea)15amp #20 Blank. If you assist me I would appreciate it.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Jan 26, 2011, 02:50 PM
    What is the question you have?

    What does this mean?

    one guys says the main shut to shut off whole panel maybe in attic or in a wall covered up?

    I highly suggest the panel be changed out, considering the age of the entire service, everything needs to be changed.

    A load study needs to be done to size the size, a 100 amp may be enough, or a 200 amp may be needed.

    You have a "split panel", top and bottom 50 amp CB should shut off each half.

    Pictures are always welcome.
    Missouri Bound's Avatar
    Missouri Bound Posts: 1,532, Reputation: 94
    Ultra Member
     
    #3

    Jan 26, 2011, 09:07 PM
    You should SERIOUSLY consider upgrading your 100 amp service to a 200 amp. Not knowing what your loads are but guessing by the size of the breakers that your panel may be taxed already. Adding air conditioning may be enough to overload the panel. Have a qualified electrician do a load calculation for you. I'd be surprised if what you have is adequate. What devices are on the 50 and 30 amp breakers?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #4

    Jan 27, 2011, 03:26 AM
    Missouri, keep in mind, two of the 50 amp breakers are the Mains.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Can I add new circuits to an old federal pacific panel? [ 2 Answers ]

Im adding about 25 new lights (recessed cans, track lighting and under cabinet lights) to an older home that has 3 federal pacific panels.

Add a second subfeed to a main panel [ 1 Answers ]

We have a 200 amp service main panel. We added a 100 amp subfeed to this panel. May we add a second 100 amp subfeed to the 200 amp service main panel?

Relocate main or add sub panel [ 0 Answers ]

We have an old cottage; raised 4' above ground, exposed to the elements, in Ontario, Canada and we would like to relocate the main 100A panel about 25 feet over to new kitchen location OR install a sub panel there instead to serve us better. What wires should we use to reloacte the main panels...

How do I add a 30amp to my circuit panel [ 3 Answers ]

How do I determine the size of my circuit panel. I want to add a 30amp plug socket for my RV hookup.

How to add 110 circuit breaker or new sub panel [ 5 Answers ]

I bought a 120v 2000 watt hot water heater. This calls for a 25 amp breaker. I only have 1 free 15 amp. Would it be better to replace the breaker or put in a subpanel? I also have my stove connected to a double 30 amp 220. Which route would be best, and could someone explain in detail how to do it....


View more questions Search