    Dining room circuit only works while dryer is running, Dryer doesn't heat up?
    Old house with knob and tube wiring. Dryer has 3wire w/ground. 60 Amp Fuse Box. With the lack of circuits there is a lot of fuses blown. Friend/owner has upped the fuses all to 30 amps and has been warned of the dangers associated. Dining works normally some of te time, but at different periods it will not operate unless the dryer happens to be running. While the problem is occurring, the dryer never heats up. Dryer works normally the rest of the time though. I did a basic check, but I couldn't find anything. Any ideas of what could be going on? I figure maybe a short, but I am still pretty unexperienced. Thanks.
    hkstroud's Avatar
    hkstroud Posts: 11,929, Reputation: 899
    Home Improvement & Construction Expert
     
    #2

    Nov 26, 2009, 07:08 AM

    If someone arbitrarily up the fuses to 30 amps and has somehow tied a dining room circuit in a dryer circuit, I say call an electrician. Without being there, there is no way anyone could reasonably access what has been done or what dangers lurk here. Call the electrician now or call the fire department later.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #3

    Nov 26, 2009, 07:29 AM
    No. Don't call an electrician. Tell your landlord/owner to call one and move out of this death trap ASAP!




    Quote Originally Posted by thayden88 View Post
    Old house with knob and tube wiring......With the lack of circuits there is a lot of fuses blown. Friend/owner has upped the fuses all to 30 amps and has been warned of the dangers associated.
    These people are IDIOTS! I guess the warnings were too subtle. Show them a picture of a house fire with burned bodies. Maybe that will get the message across!
    medic-dan's Avatar
    medic-dan Posts: 321, Reputation: 23
    Full Member
     
    #4

    Nov 26, 2009, 09:08 AM

    It sounds like it might be a neutral problem. Where? Can't tell.

    Regardless, get out of the house. The wiring is faulty and is EXTREMELY dangerous.

    Tell "Friend/Owner" to call an electrician. If he's hesitant then ask him what he would like you to say at his eulogy.
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #5

    Nov 26, 2009, 10:40 AM

    I'm thinking it could even be 1 of the Hot Legs.
    An Electrician should Check Voltage between both Hot Legs, In and out of Disconnect or Fuses, At Electrical Panel Main Lugs and Out from each Breaker.
    If 1 Hot Leg is Opened, Power can connect from 1 phase to the other.
    You should Have 240 volts between both hot legs. You will likely see close to zero volts.
    Missouri Bound's Avatar
    Missouri Bound Posts: 1,532, Reputation: 94
    Ultra Member
     
    #6

    Nov 26, 2009, 07:51 PM
    What you describe may be a backfeed condition through the dryer which allows the dining room circuit to work. If it's intermittent as you say, then you have a very dangerous condition where one of the hot wires is opening up from time to time. This is serious because wires that intermittently connect are prone to arcing, and arcing is a fire starter. Get someone qualified to work on electrical issues there now. It's an emergency. Is this your residence? Do you rent or own?. or is it a "friends"?
    thayden88's Avatar
    thayden88 Posts: 6, Reputation: 1
    New Member
     
    #7

    Nov 26, 2009, 11:11 PM

    It is a friends house. Im the one she called to look at it, but when I got there she said it started working again. I checked through all the voltages, continuity, and what not, but I couldn't find anything because everything was working fine. I just got out of tech school recently and don't have years of experience backing me up yet. I told her it was probably a short circuit or arcing condition and that it is dangerous and a fire hazard. I also told her she really should change the fuses back to original size because that was also a fire hazard. I haven't been back since, but last I heard it was still causing problems. She wants me to install a new panel to get rid of the fusebox and probably replace as much of the wiring as I can. Maybe hearing it from other sources will let her see how dangerous it really is. I'll let her know what you guys are saying. Thanks. Anything else added would be appreciated.
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #8

    Nov 27, 2009, 07:40 AM

    The time for the electrician to locate it is when it is giving a Problem, Hard to find when it is working.
    If working temporarily, Electrician should check all Main connections, They should also check for a burnt buss(where a breaker would plug onto), and that the Fuse(s) are tight. Loose connections generate heat, and you may find by discoloration.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

My dryer only works on low heat and not on high heat. [ 1 Answers ]

I have Whirlpool dryer model #TEDX640EQ1. The dryer does not produce any heat when on the high heat setting, but will get warm on the low heat setting. I need the high heat setting to work so that it doesn't take 2 cycles or more to properly dry my clothes. Anyone know what the problem could...

Dryer only works on low heat [ 1 Answers ]

I have a Kenmore dryer that only produces heat when it is on the low heat cycle. Any other setting it spins with no heat. The model # is 110.60612990

Circuit breaker OK, but no electricity in living room/dining room [ 5 Answers ]

I have a 100 year old farm home. The lights went out in living room and dining room Thanksgiving night. The circuit breaker appears normal and the panel is OK. What went wrong?

Kenmore Dryer - No Heat - Everything else works [ 2 Answers ]

Model number 11063932101 - The element will not heat, but the drum will rotate, interior light comes on, etc. I have checked the two circuit breakers - OK! I have done a continuity check on the heater element, thermal cut-off, thermostat and thermal fuse. All pass the continuity check. Also, I...


View more questions Search