    Detached garage grounding rod or not
    Hi, I just ran across another problem. I will be running 40 amps 240 volts out to my garage via underground 8-3 plus ground. Do I need a grounding rod at the garage or is the ground via the service cable to the garage enough? I have seen both and am not sure why. Is the 240 volt service to the garage required to have a grounding rod at the garage even though there is already a ground wire coming from the main service panel in the house? Any help would be much appreciated! Thanks again.
    Regards,
    Stevan
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Jun 27, 2006, 08:49 AM
    In this particular situation, a ground rod is required at the panel in the garage. The neutral in the garage panel must be isolated from the equipment ground bar, wires, and panel enclosure.

    This is the short answer, there are reasons that you have seen panels without ground rods, the explanation will be too lengthy for me to go over at this time.

    Hope this helps.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Generator grounding [ 5 Answers ]

I just bought a 4400/3500 watt generator for a building project. The directions say that I need to ground the generator with a suitable grounding rod and stranded No. 12 AWG wire. I have never heard of contractors grounding their generators. Are they being careless, or are my generator...

Detached garage pad [ 2 Answers ]

I am trying to get some information on building a garage starting with the Pad. I am planning on building a 22X26 detached garage. The rough grade was completed about 4 months ago. It is a clay base with no topsoil added yet. Should I get a bobcat in to remove a couple inches or just pack down...

Detached garage panel install, please help [ 2 Answers ]

Hi, I am running 8-3 underground in pvc conduit and am wondering: 1. How high up the garage wall I should come up before entering the garage (I guess this means how high the panel will be on the inside as well)? Any code for this or is whatever height is comfortable good enough? 2. Also, I...

Washer hook ups in detached garage [ 5 Answers ]

I would like to move my washer and electric dryer from their present location off the kitchen, to the back inside wall of my detached garage. It is approx. 35' from the back of the house, to the location in the garage. My house has no basement, but has a crawl space underneath. I 've checked...

Mice in ceiling of semi-detached house [ 1 Answers ]

Thanks for being an expert. I am a new owner of a semi-detached house. I have heard very occasional skittering in my living-room ceiling and suspect mice. I have looked both on the outside and inside the house, but can find no obvious entry point. Could the mice be in the walls and/or coming in...


View more questions Search