    RickViz Posts: 2, Reputation: 1
    New Member
     
    #1

    Jan 17, 2009, 08:15 AM
    Correct Subpanel Scenario
    "#5. No ground rod is needed (and should not be installed) as long as an green equipment ground wire is pulled,(recommended and standard practice). The green wire connects to the equipment ground bar in the panel, which is bolted to the panel backbox. The neutral remains isolated on the neutral bar. Be sure the neutral bar is not connected to the panel backbox."
    That is a quote from tkrussell in his reply of 9-26-06 to metagami.
    I want to make sure this will apply to my situation. From what I've gathered from this forum and from "tk", is this good to go:
    1) my electrical need for my detached garage workshop would be... a 12A dust collector running the same time any given woodworking machine is running, up to a 120v 20A drum sander (I'd put the dust coll. On it's own 20A breaker; the other machines on another 20A breaker-- only one would ever be on at a time); a circuit for lights (3 sets of 48" dbl flourescents and a couple small 14 watt energy saver flourescent bulbs; and possibly on this same 20A breaker circuit, a 120v window AC unit, about 10-12,000 BTU (?)

    2) 60A breaker in the house's main breaker; 3#6 copper wires (2 blacks, 1 white) and 1#8 green equipment ground wire, about 65 feet to the garage, into either 1 1/4" PVC pipe 18" down, or steel or aluminum conduit 12" down; 3 20A breakers in the subpanel, isolated neutral buss...

    Will this work? No ground rod necessary? Thanks
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #2

    Jan 17, 2009, 02:24 PM

    Be Careful of the context that you are using with TK's statement.

    I suspect that he stated that this is true when the subpanel and the main panel are in the same building.

    Once you go to a remote building, then you are required to sink a ground Rod and connect the equipment grounding conductor.

    However, the ground rod is intended to dissipate lightning not to act as an electrical ground for the circuit.

    You also have to make sure the "Grounded Conductor" (White) (Neutral) is insulated from the grounding system on the subpanel.
    andrewc24301's Avatar
    andrewc24301 Posts: 374, Reputation: 29
    Full Member
     
    #3

    Jan 17, 2009, 03:00 PM
    Quote Originally Posted by donf View Post
    However, the ground rod is intended to dissipate lightning not to act as an electrical ground for the circuit.
    And for some more really good information about "grounding", we blew the lid off the subject in this tread:

    https://www.askmehelpdesk.com/electr...ke-300160.html
    RickViz's Avatar
    RickViz Posts: 2, Reputation: 1
    New Member
     
    #4

    Jan 17, 2009, 04:52 PM
    Don, thank you for your response. I'm clear now about the ground rod, also on isolating the neutral buss. Is my choice of (60A) breaker and #6 wire OK, for 3 20A breakers in the subpanel? Lastly, would it be less expensive to use a GFI 60A breaker or 3 20A GFI's?
    Thanks

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Matching up the correct capacitor with the correct condenser fan motor? [ 4 Answers ]

How crucial is it to match the right capacitor to the right condenser fan motor? If you have the wrong capacitor, can this cause the motor to stop after running for a while, say 20 or 40 minutes? It would start up again, but would allways stop. The specs for the motor are: Emerson E-line, model no...

Fictitious Scenario [ 9 Answers ]

Assume that my friend Joe purchased credit reports from John for 50$. One of them was about Mike. Joe uses the identification info on Mike's report to take out a home equity loan. What crimes did my friend Joe commit? -CsX

Scenario [ 2 Answers ]

How do I install a 150W driveway light 200m from the house, the light switch is on the wall outside the front door under the porch

NY, NJ, PA tax scenario [ 3 Answers ]

Wife works in NYC, lives in NJ I work in NJ and live in NJ. Just got married so next year will be the first time we file together. Considering buying a home in PA and both would continue to work at our current jobs. Combined income: over $200K Generally speaking how would the move to PA...

Solve this scenario [ 4 Answers ]

Scenario You are one of a team of managers working in popular hotel. You are responsible for the smooth & efficient running of the hotel kitchen. Within the kitchen you have 3 chefs & 8 kitchen assistants who carry out a variety of tasks supporting the chefs. Other managers within the hotel have...


View more questions Search