    Connecting 240v heater to 2 - 1 pole breakers
    I have 2 - 15amp tandem breakers - both are 1 pole. I know that normally you would use a 2 pole breaker to create a 240v feed to the heater. However, if I connect my 12-2 wire to the 2 different breakers, I get 240v and my heater works correctly. Is there any problem to doing this rather than using a double pole breaker?

    Thanks
    Peter Kwan's Avatar
    Peter Kwan Posts: 26, Reputation: 1
    New Member
     
    #2

    Jan 5, 2007, 02:43 AM
    This is very dangerous for people who perform service for the heater in the future, you have to make sure they turn off both breakers before any service work, if they get injure or kill, you may be held responsible for it, you should replace it with a double pole breaker.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #3

    Jan 5, 2007, 03:19 AM
    Also with a 2 pole breaker the 2 poles are tied together called a Common Trip, if one side shorts out, the other pole trips also,without it the circuit/pole is still alive.

    Spend the 8 bucks and do it correctly and legally.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

120V heater tape off a 240V source. [ 3 Answers ]

Hi, My question is very similar to HandyJohn's and much my question was answered in is post. Mostly verifying my suspicion of needing a step down transformer here. Just wondering if you know of any simpler options I may be overlooking outside of running a dedicated line. Here's my...

Converting 240V thermostat to programmable [ 1 Answers ]

Recently purchased a low-voltage programmable thermostat for the girlfriend to replace her ancient Cadet model but found it was unusable as she has a 240V (Single black, single red + ground wire) in-wall electric heater. Are there programmable thermostats for this type of system or do they only...

Wiring 120V light from 240V source [ 6 Answers ]

I currently have a well house that has a 240V source on 12-2 wire powering a submersible well pump. I would like to wire in a 120V light. Can this be done using the 12-2 wire already in place or do I need to remove the 12-2 wire and install 12-3 wire? (It is approximately 60ft from the main house...

Installing double pole wall t-stat baseboard heater [ 2 Answers ]

I have a 220 baseboard heater, and it is on dedicated circuit. Heater works okay as I have run wires straight through and turned on circuit breaker and heater works. This is a Marley baseboard heater and wall double pole thermostat. Instructions with thermostat leave a lot to be desired. Actual...


View more questions Search