    Conduit sizing for wire
    I would like to pre run underground conduit for a future above ground SPA. Load is 50-60 amps and location is about 100 feet from the main panel. Conduit would eventually be used to feed a sub panel at the spa location.

    What size wire would be suggested and then what size PVC conduit could be used to pre-plumb this run?
    Missouri Bound's Avatar
    Missouri Bound Posts: 1,532, Reputation: 94
    Ultra Member
     
    #2

    Dec 14, 2009, 06:18 PM
    Is this a 120v or 240v installation, or does it require both?
    As far as wire size, it'll be either #6 or #8, depending on what the spa actuallyrequires. 1" will make it easy for either, assuming you are pulling 4 wires. The tub MFG. will tell you what size circuit to provide. (50 amps seems a bit high to me)

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Wire sizing and conduit sizing [ 8 Answers ]

I am looking for confirmation on some of the info I have found and answers to a few missing pieces. This is regarding wire size and conduit size for service conductors from the meter to the breaker panel (about 30 ft away). Wire Size: 125A service needs #2 copper or 1/0 aluminum -- #6 copper...

Conduit sizing [ 2 Answers ]

How many #16 conductors and #18 twisted-pair cables can I put into a 2" EMT conduit?

Conduit Sizing and Wire Type [ 10 Answers ]

Hi folks, The application here is to get power to a landscape area (4'x4') for decorative lighting purposes. The overall landscape design calls for up to five of these areas to be lit - at some point. The furthest one from the house will be 300 ft. I'm looking for least expensive recommendations...

Conduit sizing [ 1 Answers ]

I have 4 conductor tray cable , 3 number two and one # 6 bare ground in a jacketed tray cable, would 1 1/2 rigid conduit be suficient for this application, it runs about 200 ft

Conduit sizing? [ 4 Answers ]

Hi all! I am relocating my breaker box approx 30 feet from its original location. Installing splice box in the old location for connections. My question is : I have 14 12-2 and 3 12-3 to pull from new box to splice box what size conduit do I need so not to worry about heat build up or de-rating...


View more questions Search