    jaiseb06's Avatar
    jaiseb06 Posts: 1, Reputation: 1
    New Member
     
    #1

    Jan 26, 2011, 09:10 PM
    Code violation electrical
    I am doing some inspection on some electrical work done on some commercial building. The first thing I noticed was in the ceiling someone used a nonmetallic cut-in box with drywall wings to put a recept in the ceiling tile. I know it is a code violation I just can't find it I need some guidance.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Jan 27, 2011, 03:38 AM
    I don't see a problem with how the receptacle is installed. The issue should be is non-metallic cable allowed in the ceiling plenum of a commercial building.

    You will need to review Section 334.10 of the 2008 edition of the NEC, and determine the type construction the building is classified.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #3

    Jan 27, 2011, 04:10 AM

    NM cable is not allowed above a drop ceiling in a commercial space, regardless if it is a plenum air space or not.

    Who are you inspecting this for and under what authority?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #4

    Jan 27, 2011, 06:36 AM
    Stan, I responded as I did as first the inspector should know that NM is not allowed above a suspended ceiling in commercial buildings, and of course, there are certain states that waived this requirement.

    They thought it was silly that NM is allowed in the partitions, but not in the ceiling, of certain type construction.

    And I meant just the space above a suspended ceiling, not specifically air plenum space.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #5

    Jan 27, 2011, 07:52 AM

    Ah, no problem.

    I am wondering what type of "inspection" the OP is doing.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #6

    Jan 27, 2011, 08:54 AM
    Same here, that is another reason why I was vague.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Nyc electrical code [ 1 Answers ]

When installing recessed lighting in a roof soffit what type are required? IC or non IC . Same for a installation where there is a attic above?

What code applies to subfed panel in the electrical code [ 1 Answers ]

What section of the code (electrical) applies to subfed panels

Reporting labor code violation [ 2 Answers ]

My now ex-boss violated some labor codes. She fired me over the phone. Which obviously leads to not having my check. And then that leads to not having my check or letting me know when or where I'd get it for three days. How do I report her violations?:mad:

Is this a health and code violation [ 4 Answers ]

First of all the swimming pool and the laundry room has sewage coming out of it Second the wiring is aluminum and it is burning up the electrical outlets and light switches Third 7 apartments have black mold and some of them have levals of carbon monoxide

Air Gap Code Violation [ 19 Answers ]

So I am renting a condo from someone, and recently the garbage disposal completely broke. It had been leaking massively and was apparently corroded and irreparable. I live in Washington DC, and when the plumber came to fix everything he said that there was an Air Gap Code Violation and he had to...


View more questions Search