    jduke44's Avatar
    jduke44 Posts: 407, Reputation: 44
    Full Member
     
    #1

    Jun 16, 2005, 05:28 PM
    Circuit breakers
    It seems so far that our kitchen is wired all on the same circuit. When we use the oven and microwave or the microwave and the toaster oven which is on the other side of the room the breaker trips. That breaker is currently 15amps. Would it be all right to change that breaker to a 25 or 30 amp for the time being until I can trace the wires to separate them? Should the gas range and microwave be on its own circuit?
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #2

    Jun 16, 2005, 08:20 PM
    Chances are the circuit is wired up with # 12 wire and you could safely change to a 20 amp breaker. If you can get a look at the right place on the wire, it will say something like 12-2 with ground. If it is only 14 gage, stick with the 15 amp breaker.

    I wouldn't worry about the gas range and microwave. Most gas ranges only have a light and a timer that draw very little current.
    jduke44's Avatar
    jduke44 Posts: 407, Reputation: 44
    Full Member
     
    #3

    Jun 17, 2005, 12:16 PM
    Circuits
    Thanks, labman, I will take a look at that. I remember someone telling me that a microwave should be on its own circuit. I wouldn't have worried about it if that was all it was but sense it seems the whole kitchen might be wired on the same I probably should get some of the wires off there. Buit for the time being I will make sure it is a 12 gage before I change it. Thanks again.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Trane Air Condition circuit breakers trips [ 7 Answers ]

I have a Trane Air Condition that refuses to run more that 10 minutes without tripping the circuit breaker when tempertures are below 32 degs. I read that at low tempertures, more features are needed to keep the heat up. Operation of these features seems to overload the circuit. There must be a...

Recepticals and breakers [ 1 Answers ]

How many receptical can be put on a 20 amp breaker? Also would it be okay to put lampost lights on a breaker that services my basement? The total wattage would be 1055 watt. Thank you, Don

ARC fault breakers ? [ 4 Answers ]

I see where the 2005 NEC requires ARC fault breakers on all bedroom circuits,lighting and wall recepticals. It appears that this is for new construction. Would this also apply to rewiring an old house? Thanks in advance. Tom

Outside GFI circuit - 15amp outlet on 20amp circuit [ 1 Answers ]

I need a better understanding of what I should do when setting up my new outdoor circuit. I've got a circuit that runs about 150 feet, so I'm installing 10g wire to allow for the voltage drop. I read in the Home Depot Electrical 123 book that I can have at most a 15amp circuit with 10g wire on...

Circuit breakers [ 2 Answers ]

I would like to up grade the amps going to my garage so I can run my saws and power tools with out dimming my shop lights. I currently have a old style fuse box in the garge feed with 12ga uf cable run off a 20amp circuit breaker in the service panel. My plans are to replace the fuse box with a new...


View more questions Search