    Can I run a power cord conduit
    I have a residential sewage pump station in the front of my house.
    It’s a 300 Gallon concrete pump chamber.
    In it, there is a Gould (Model 3886) Submersible sewage pump with a 220v plug that gets plugged into a SJERhombus Super Single pump switch that has a piggyback plug. That plug in turn gets plugged into a 220V single outlet plug
    That is mounted inside of the tanks neck (yes I did say inside the tank, I am assuming that 19 years ago the residential code for this type of installation allowed this).

    From the house side there is a junction box that has the end of the source line (NM Cable) hardwired to THWN line in the conduit. The THWN wires into the tank outlet are in the 3/4” pvc conduit approximately 14” below grade. The conduit run is 14’.

    So after replacing the outlet 5 times, the pump and pump switch 2 times due to corrosion. After my last inspection
    Looks like I will need to replace all 3 soon. Not wanting to climb back into the tank again to fix/repair this.

    I would like to purchase a new pump and pump switch both which come with SJTOW,SJOW power cables with bare leads in optional lengths (30 feet in this case). I would like to run the two power cables in the pvc conduit and into the junction box on the side of the house and make my hard wire connections there and remove the outlet in the tank. So the question is can I run the described power cords in the PVC Conduit? Or do I need bigger conduit and if so what size?

    Power cords. Specs below.
    The pump switch power cord is a 230V 14G 2 Conductor (SJOW) and the pump cord is a 230v 16/3 cord (SJTOW).

    Please let me know if I have left out any information that is needed…
    Thank you in advance.
    Sante
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Dec 23, 2009, 07:16 AM

    Outlets in sewage tanks for pumps have always been a problem with corrosion.

    What has been done before is to terminate the cords in a junction box, either on a post, or in the ground with the cover flush with grade.

    You plan is fine, not too long a distance.

    Cord does not pull through conduit very easily due to the friction of the materials. I think a 1" conduit should hanle these two cords without too much difficulty.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Can I run a electrical line in the same conduit as phone and cable? [ 9 Answers ]

Aloha All, I built a little 8'x12' office that is approximately 185ft from my main house. I was planning on running a electric, phone, and cable line in an underground conduit from my house to the office. Can I just use 20A romex for the electrical line that will be tapped off an exterior...

Long power cord [ 4 Answers ]

OK you can't leave an extension cord in place over 90 days. So as long as the wire size is OK for the load at that length, can I buy a 20' one, cut the end off and hardwire it in as a 20' power cord? I am talking a motorized screen for in a church. The directions say 14-18 wire. I should be...

Do I need conduit to run a 220v cable through my cellar? [ 10 Answers ]

I'm running a 2-2/4 aluminum cable for a 220v circuit from my barn from the panel in my house. Once entering the home (from the 36" deep in-conduit run from the barn), I have to string the cable through the mechanical area (cellar) of the house, then through a center-home crawl space and then...


View more questions Search