    Can run 2 no 12AWG lines from range outlet box with 2 t'stats and 2 basebrd units
    Hello,
    I have an existing range line (not in use) that has a 40 amp breaker and 8 AWG double pole line from the service panel
    Can run 2 no 12AWG lines from range outlet box with 2 t'stats and 2 basebrd units (750 and 1200 watts) then downsize the breaker in the service panel to 20 Amp?

    Thanks
    Missouri Bound's Avatar
    Missouri Bound Posts: 1,532, Reputation: 94
    Ultra Member
     
    #2

    Jul 14, 2010, 05:39 PM

    You can't mix wire sizes in a circuit.. You can pull the 8 out and replace it with # 12. MIs-matching breakers and wiring is also not a good idea... leads to confusion and ultimately incorrect protection on a circuit or device. You need to run new wire and properly protect it and the heaters with the appropriate breaker. Is it your intention to run these heaters on 120 or on 240 volts?
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #3

    Jul 14, 2010, 05:42 PM

    Actually mixing wire sizes is frowned upon, but not at all prohibited.
    What you propose is fine, the only thing I would do is label the wires at the panel to avoid future confusion.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Can you run 14AWG wires off a 12AWG line? [ 8 Answers ]

I just bought a new house and was repairing a broken wire that I found in the basement. The broken wire was 12AWG and runs directly off a 20amp breaker. When I opened the junction box, I found that, the 12AWG line splits into two other lines (one goes to a light in the basement, and one goes...

Wiring a ceiling fan in middle of run, outlet at end of run [ 5 Answers ]

I am wiring a bedroom ceiling fan and just needed someone to help me figure out part of the wiring I'm not sure about. The goal is to have a 2 gang switch control the light and the fan separately. The switch is at the beginning of the run, then the ceiling fan, and then I also have an "always...

What is the blue 12awg wire attached to in the box? [ 6 Answers ]

I have a hot tub with 4 wires coming from the hot tub controls to be attached to the shut off box 8 feet away. Two wires, one blue, one red are 10awg, apparently 110volts each incoming. Two additional wires, one blue, one red are 12awg and would appear to be for the second cirucuit, with a 15 amp...

New 4 wire Dryer/Range Outlet [ 8 Answers ]

I have an older style breaker panel where the neutral & ground wires are connected at the same strip! I plan to upgrade the panel to a 4 wire system with a separate neutral & ground, However since I also need to have the service entrance line upgraded also it won’t be until later this year before I...

Recessed Range Outlet... [ 1 Answers ]

Hello Group, & TK!:D I was wondering if I can install a Range outlet by just nailing the outlet between 2 nailers and if I truly need a box, and if I do, what size box should I use, because the standard junction, ceiling, and outlet boxes don't seem to fit on the outlet itself. Any help really...


View more questions Search