    Can I run a 12/3 from an 8/3 circuit?
    I am remodeling the kitchen and don't have an easy way to pull a new circuit from the breaker box. I do have a new 8/3 wire from the breaker box to the kitchen though. Can I run this to a metal box and then run a 12/3 (bx) through the inside of the cabinet for the new electric cook top?
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #2

    May 14, 2008, 04:32 PM
    You can, but it then needs to be on a 20 Amp breaker.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #3

    May 14, 2008, 04:49 PM
    What is the rating of the cooktop??
    Washington1's Avatar
    Washington1 Posts: 798, Reputation: 36
    Senior Member
     
    #4

    May 14, 2008, 05:04 PM
    Quote Originally Posted by stanfortyman
    What is the rating of the cooktop???
    Same question I have??

    Also, If you decide to do this, you may want to leave some sort of information letting someone know that the circuit is no longer a 40A circuit.
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #5

    May 14, 2008, 05:46 PM
    Being on a 20 amp 2 pole should clear up any misunderstanding as well as identify the panel. I would think 30 or 40 Amp for Cooktop. They do make 20 amp.
    I think people would be surprised you could have a portable spa with heater, blower and jets, and work on a 15 Amp recepticle/250 Gallons?
    I would like to believe Poster knew that #12 is what he needed. If he's not sure The Nameplate Rating will be helpful.
    Only this Cooktop can be connected, and not any previous appliances.
    The way I was reading this was for something, now it is for something else, the 20 Breaker would solve this, and the metal box needs to be grounded. Good Luck
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #6

    May 15, 2008, 06:00 AM
    Generally speaking, a range top will be 30 amps. A range/oven combination will be 40 amps.

    With either type unit, the circuit should be an independent circuit and as such it should not be used as a feeder to at 20 amp, #12AWG.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Theory of vacuum Circuit Breaker & sf6 circuit breaker [ 15 Answers ]

I want to know about the basic Theory of vacuum Circuit Breaker & sf6 circuit breaker

AC circuit [ 1 Answers ]

For the given figure(attached), the current drawn through the inductor is .9A while the current drawn through the condenser is .4A. Find the current drawn from the source.

Changing 15 amp circuit to 20 amp circuit [ 4 Answers ]

I just bought a house with a jaquzzi that was installed by the previous owner. It appears that they wired it to an existing circuit run that is only pulling 15amps. So if the lights are on in the bath room and in the closet, when we turn on the jaquzzi it trips the breaker. Before I open up the...

Converting 15 anp circuit into 20 amp circuit [ 1 Answers ]

I just bought a treadmill. The problem is it doesn't work where I want it to. It can only run on 20 amps but all my outlets use 15 amps. It keeps tripping the breaker. Can I easily convert my outlet to a 20 amp?

Outside GFI circuit - 15amp outlet on 20amp circuit [ 1 Answers ]

I need a better understanding of what I should do when setting up my new outdoor circuit. I've got a circuit that runs about 150 feet, so I'm installing 10g wire to allow for the voltage drop. I read in the Home Depot Electrical 123 book that I can have at most a 15amp circuit with 10g wire on...


View more questions Search