Ask Experts Questions for FREE Help !
Ask
    bpwarne's Avatar
    bpwarne Posts: 2, Reputation: 1
    New Member
     
    #1

    Jul 3, 2010, 01:37 PM
    Can I just replace the breakers?
    I have a 40Amp breaker at the box on the circuit for my cooktop. I also have a 30amp breaker on the circuit for my single wall oven. Both circuits have what appears to be #6 wire. Wire is a bundle of 7 .060" wire solid wire conductor and diameter of bare bundles is .170-.180". Why would house be wired with what I assume is 50A wire and have smaller breakers? I am wanting to put in a 50A cooktop and a 40A double wall oven. My assumption is that I can just replace the ckt breakers, theat the wiring is fine for 50 Amps. The 40 Amp run is probably about 45 foot and the thirty Amp run is about 40 foot.
    cdad's Avatar
    cdad Posts: 12,700, Reputation: 1438
    Internet Research Expert
     
    #2

    Jul 3, 2010, 03:17 PM

    The problem is the service you have. If you have everything in the house running at once you could overload the wires and cause a fire. How many amp service do you have from the main power panel and how much do you have in circuit breakers under that?
    bpwarne's Avatar
    bpwarne Posts: 2, Reputation: 1
    New Member
     
    #3

    Jul 3, 2010, 05:48 PM
    Comment on califdadof3's post
    I have 200 amp service box with I assume tobe a total of 430amp in breakers. The oven has two 30 amp breakers, the cooktop has two 40 amp breakers. Do I count them as 30 and 40 amps total respectfully or do I count them as 60 amps and 80 amps respec
    cdad's Avatar
    cdad Posts: 12,700, Reputation: 1438
    Internet Research Expert
     
    #4

    Jul 3, 2010, 06:01 PM

    bpwarne : I have 200 amp service box with I assume tobe a total of 430amp in breakers. The oven has two 30 amp breakers, the cooktop has two 40 amp breakers. Do I count them as 30 and 40 amps total respectfully or do I count them as 60 amps and 80 amps respec


    I would assume that the cooktop and oven are 220. And the service is 220. So having a total of 430 amps worth of breakers your already at the limit for your service. At 200 amp anything running on 220 counts directly against the amp count. Anything on 110 would be 1/2 of the amp count for calculating load on the original 200 amp service.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #5

    Jul 4, 2010, 04:51 AM
    A conductor with 7 strands of .060 wire would seem to be #6 AWG. Therefore, you are correct that the cable can handle 50 amp max. So you should be able to use this cable for both the 50 amp and 40 amp feeders to the new appliances.

    I have no idea what the answer you have received already means.

    Adding circuit breaker amp ratings of all branch circuits in a panel means absolutely nothing.

    The standard voltage in the USA is 120 and 240 volts.
    cdad's Avatar
    cdad Posts: 12,700, Reputation: 1438
    Internet Research Expert
     
    #6

    Jul 4, 2010, 05:45 AM
    Quote Originally Posted by tkrussell View Post
    Adding circuit breaker amp ratings of all branch circuits in a panel means absolutely nothing.
    Here is where we are going to disagree. I think it may be a misunderstanding. Each branch circuit represents a "load". It's a potential of value. So if you only have 200 amps to work with. Then the potential amps to be distributed is also 200 amps maximum without exceeding the rating. So yes it does matter if that is how the circuit is designed. There is always the planned potenial for everything to be "turned on" at one time. That is why it is important.

    Hope that makes more sense to you now.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #7

    Jul 4, 2010, 06:46 AM
    Quote Originally Posted by califdadof3 View Post
    Here is where we are going to disagree.
    Then you are disagreeing with every qualified professional electrician out there.
    The sum of the breakers is a MEANINGLESS number!


    Quote Originally Posted by califdadof3 View Post
    Then the potential amps to be distributed is also 200 amps maximum without exceeding the rating. So yes it does matter if that is how the circut is designed. There is always the planned potenial for everything to be "turned on" at one time.
    Completely false. The calculated load is what is planned for. NOT that everything in the home will be turned on at once.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #8

    Jul 4, 2010, 06:46 AM
    You can disagree with me all you want, and try to justify your advice, however, it is still incorrect.

    Read Article 220 of the National Electric Code, understand how each branch circuit is sized, and how a service sized sized, you will see that adding amp ratings of circuit breakers is irrelevant.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #9

    Jul 4, 2010, 07:31 AM

    Amen!
    cdad's Avatar
    cdad Posts: 12,700, Reputation: 1438
    Internet Research Expert
     
    #10

    Jul 4, 2010, 07:36 AM
    Quote Originally Posted by tkrussell View Post
    You can disagree with me all you want, and try to justify your advice, however, it is still incorrect.

    Read Article 220 of the National Electric Code, understand how each branch circuit is sized, and how a service sized sized, you will see that adding amp ratings of circuit breakers is irrelevant.
    Quote from article.
    The branch-circuit loads are combined with other applicable demand factors in Parts II, III or IV to determine feeder and/or service loads

    Ref:

    Electrical Contractor: Article 220-Branch Circuit, Feeder and Service Calculations


    Maybe I wasn't explaining myself right. But this says the same thing. The advice I was giving is based on worst case and not to exceed.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #11

    Jul 4, 2010, 08:05 AM

    Cal,

    There are two type of loads:

    Connected load - the physical wiring.

    Calculated Load - The anticipated load at any given time.

    All circuit sizes are based on the calculated load, not the connected load.
    cdad's Avatar
    cdad Posts: 12,700, Reputation: 1438
    Internet Research Expert
     
    #12

    Jul 4, 2010, 08:08 AM
    Quote Originally Posted by donf View Post
    Cal,

    There are two type of loads:

    Connected load - the physical wiring.

    Calculated Load - The anticipated load at any given time.

    All circuit sizes are based on the calculated load, not the connected load.
    Then that was my misunderstanding. I appologize.
    Missouri Bound's Avatar
    Missouri Bound Posts: 1,532, Reputation: 94
    Ultra Member
     
    #13

    Jul 4, 2010, 09:57 AM
    BPwarne... have we totally confused you yet?

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Replace main 100 amp breakers [ 1 Answers ]

Can I replace the 100 amp main pushmatic breakers with a different more available type?


View more questions Search