    nwalter's Avatar
    nwalter Posts: 11, Reputation: 1
    New Member
     
    #1

    Aug 31, 2010, 07:03 PM
    Can I have 21 recepticals, 10 lights, 3 fans, and 3 (240v) plugs on 100 amp breaker?
    I just bought a 100 amp breaker panel to replace an old fuse panel. The thing is, after I figured up everything I wanted in the shop, (21 receps. 10 lights, 8 switches{4-3way switches and 4-single}, 3 fans{2 w/ lights}, and 3-(240v)plugs), I'm now not sure if I can pull all them on a 100 amp panel. And how would I figure that up to know. I really need to know soon. Thanks, Nate!!
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #2

    Aug 31, 2010, 07:17 PM
    The only thing you mention that has any draw is the lights and fans. Even they are not that big of a load.
    Switches do not draw anything.
    Receptacles only have a draw when something is plugged in, even the 240v ones. ;)

    The only accurate way is to do a demand load calculation. Not the simplest thing for a DIY.
    If this is for a house then ALL the general use receptacles and lighting are taken into account in the load calc. The actual number of them is meaningless.

    I can tell you from experience, what you have is FINE on a 100A panel.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #3

    Aug 31, 2010, 07:17 PM

    Your layout process is out of whack.

    To begin with, this 150 Amp sub-panel requires a four wire feed from the main panel.

    If the sub-panel is going to be in a different building from the main service panel, then you must also install a complete grounding system at the sub-panel.

    You will also have to isolate the Neutral Bus from the Ground bus and Neutral cannot make any contact with the sub-panel cabinet.

    It is also mandatory that if you run power to an attached building, you must put a light outside the entry door.

    The required amperage is determined by calculating the required load, not by counting up devices you think you may need. Also, receptacles in a garage or shop need to be GFCI protected either with a GFCI receptacle or a GFCI breaker protecting the entire circuit.

    This is not a simple calculation to do so I recommend that you get at least three licensed electricians to bid on this job.
    hkstroud's Avatar
    hkstroud Posts: 11,929, Reputation: 899
    Home Improvement & Construction Expert
     
    #4

    Aug 31, 2010, 07:25 PM

    How many circuits are in the new panel? I only see you needing about 7 or 8 circuits. You have to think about how your are going to be using your tools. Are you only one person? You can have three table saws, two drill presses, a lathe and a band saw, but unless you are faster than I am you will only use them one at a time. What kind of fans, ceiling fans with light kits. Compressor, dust collector?

    What is size of breaker in main panel? What is size of present fuses box?
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #5

    Oct 4, 2010, 08:35 AM

    I'm out of whack! Why?

    Are you saying that you are running a new service to this building, because if you are, than you left that out of your initial post. Maybe you should provide decent information on what you are trying to do rather then leave everything open ended.

    But regardless of that, you would should still have do a load calculation to make sure you have the correct breaker or main cut-off installed.

    If you do not understand what I wrote or want more information on why I wrote it, how about asking me before you slam me.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Adding a 200 amp breaker pannel to feed two 100 amp pannels [ 13 Answers ]

Hello all, This is my first post so I hope I do it right. This is what I got. The drop from the pole comes down to one 200 amp meter. The 200 amp meter feeds only one panel with a 100 amp input breaker and has many breakers that power the house (stove, water heater, dryer, outlets). Then it...

How many plugs and light fixtures can be on one 15 amp breaker [ 0 Answers ]

I am fixing upm basement as a family playroom need to how many plus and light fixtures I can put on one 15 amp breaker

240V 20 amp circuit breaker [ 5 Answers ]

I'm installing 240 volt in-floor heating mats. The amperage draw is 21 amps. I intended to connect them to a 2-pole, 240 volt, 20 amp breaker. My thought was that you have two legs of 20 amp power (40 amps total). Is this correct of how the 240 volt breakers work?

240V 20 amp circuit breaker [ 1 Answers ]

I'm installing 240 volt in-floor heating mats. The amperage draw is 21 amps. I intended to connect them to a 2-pole, 240 volt, 20 amp breaker. My thought was that you have two legs of 20 amp power (40 amps total). Is this correct of how the 240 volt breakers work?

Running 2 100 amp breaker boxes on 200 amp meter base [ 1 Answers ]

I have 2 100 amp breaker boxes,but the meter base is 100 amp.Wanting to put 200 amp metet service with disconnect box.Can some one tell me if this is possible.and how you would connect the 2 breaker boxes to the disconnect box.Thank you


View more questions Search