    Can I get 120 volts from a 208v 4-wire service?
    Changing out 208v high bays to 120v LED high bays. I want to know if I can just jump off one leg of the 208v for my 120v fixture.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Apr 8, 2010, 07:45 AM
    The entire circuit needs to be converted to 120 volts, assuimg you have a 120/208 Volt WYE system.

    One leg of the 208 volt circuit can be used, and the other needs to be taken off the circuit breaker and connected to the neutral bar.

    The 2 pole breaker for the 208 volt circuit then needs to be replaced with a 1 pole circuit breaker rated for the circuit wire size.

    Of course, the circuit amps needs to be rated properly to handle the new load, which being LED should be minimal.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

120 Volts -> 1820 Watts -> 15 Amps ->#12 Wire [ 3 Answers ]

What's wrong with the combination of components in the title? The issue I have may not actually be a problem but I'm curious to get another opinion nevertheless. I had to find a circuit to connect an electrical sauna in the basement. The 1840 Watt sauna required a dedicated 120 Volt, 20 Amp,...

Stratmando, thanks I don't have 120 volts between Hot and Neutral. I have 120 volts [ 2 Answers ]

Stratmando, thanks I don't have 120 volts between Hot and Neutral. I have 120 volts between hot and ground Also have 120 volts between Neutral and ground How far in the wiring do these types of problems reach into the wall?

600 Amp 120/208V ,3Phase 4wire, Main Lug Only Service [ 3 Answers ]

Is there still a six throw rule in the NEC that would allow for a 600 Amp 3 Phase 4 Wire 120/208 Volt Main Lug Only Service or am I required to install a main breaker. The CT cabinet is a couple of feet away.

220 volts to 120 volts [ 5 Answers ]

I currently have a 220 volt/30 amp service to an electric washer/dryer combination. The washer/dryer broke down and I will be switching to individual units each requiring a 120 volt/15-20 amp supply suggesting a separate circuit. The current unit had a four wire configuration (2 hot -...

120 volts vs 240 volts tools [ 3 Answers ]

How do I configure a 120 volts 60hz woodworking tools bought in the usa to work on a 240 volts 50hz power rating in my country without having to compromise the motor operation. I understand that the stepdown transformer can only reduce the voltage but not the cycles. That means that a tool with...


View more questions Search