    Breaker question?
    How is everyone one doing? I am new to this site seems like there a lot of good information on hear. So I own my home. I was just curious is per say I have three 15amp breakers, Can I just swap those 15amp breakers with 20 amp breakers or do I have do do some wiring. Hence need an electrician? Any help is apprecciated
    RickJ's Avatar
    RickJ Posts: 7,762, Reputation: 864
    Uber Member
     
    #2

    Aug 3, 2006, 02:24 AM
    The best answer is NO. You risk a fire hazard.

    Now, if you have 12 gauge wire from the breaker to EVERY circuit fed by it, then you're OK with a 20 amp breaker, but verifying that you have 12 gauge wire for the entirety of the circuit is next to impossible.

    If you're asking because you're tripping breakers a lot, then yes, you need to get an electrician in there to give you some options.
    wildcat6's Avatar
    wildcat6 Posts: 1, Reputation: 1
    New Member
     
    #3

    Nov 17, 2006, 07:50 PM
    Does anyone know if it is acceptable to use 12 ga wiring with a 15 amp breaker? I know 14 ga is supposed to be used but I was wondering if it is OK to use larger gauge. I need to add some lights in the basement and I have 12-2 NM wire and would like to us it.

    Thanks...
    andrewcocke's Avatar
    andrewcocke Posts: 439, Reputation: 22
    Full Member
     
    #4

    Nov 17, 2006, 08:38 PM
    Yes you can use 12 ga with a 15 AMP.

    Also, if your 15 amp breaker is tripping a lot, you can pull an AMP draw on the circuit, its possible that the breaker may have gotten weak. If you replace it, you can only replace with another 15 amp breaker if you have 14 ga wire in the circuit.
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #5

    Nov 17, 2006, 08:42 PM
    Quote Originally Posted by wildcat6
    Does anyone know if it is acceptable to use 12 ga wiring with a 15 amp breaker? I know 14 ga is supposed to be used but I was wondering if it is ok to use larger gauge. I need to add some lights in the basement and I have 12-2 NM wire and would like to us it.

    Thanks...
    No problem, go for it. I have #10 connected to a bunch of my 20 amp breakers.
    wirepro's Avatar
    wirepro Posts: 2, Reputation: 1
    New Member
     
    #6

    Nov 18, 2006, 10:37 AM
    You can always upsize on the wire,but never downsize..
    uiguy's Avatar
    uiguy Posts: 9, Reputation: 1
    New Member
     
    #7

    Nov 19, 2006, 09:23 PM
    Quote Originally Posted by wildcat6
    Does anyone know if it is acceptable to use 12 ga wiring with a 15 amp breaker? I know 14 ga is supposed to be used but I was wondering if it is ok to use larger gauge. I need to add some lights in the basement and I have 12-2 NM wire and would like to us it.

    Thanks...
    By "add some lights", I assume you mean running a new circuit to a new breaker. If so, go for it. Make sure the same gauge of wire is used throughout the entire circuit, and that the breaker size meets your electrical code re. the type of circuit. I do not know your electrical code, but a lighting circuit might require a 15amp breaker. I'm not sure about a mixed outlet/lighting circuit. Regardless, with respect to the wire, you're good with 12ga.
    Now if you mean extending an existing 15amp circuit to a few more junction boxes, I'd say no. If the existing wire is 14ga, and you add a stretch of 12ga wire, life is good until 5 years later someone mistakenly ups the breaker to 20amps assuming that the entire circuit is 12ga. Always assume the worst.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Gfi breaker [ 1 Answers ]

I have an outdoor pond. I think that my electrical connection got wet and shorted out. My question is, I changed out all the receptacles on the gfi circuit and only two work. Is it possible that the breaker is bad and does not supply all of the circuits now??

Breaker Box Question [ 5 Answers ]

I guess it would be better to call it a fuse box... not breaker. I live in a rather old house with k&t wiring. Our box, located in the basement, has all the wiring come in from the top. At the top of the front panel there are two black pull-out things that have markings saying main and off. They...

Breaker [ 5 Answers ]

I have low voltage landscape lighting plugged into an outside outlet. The total watts is about 500 and I am using a 600 watt transformer. The outlet is a GFI outlet and has a dedicated 20 amp breaker. Nothing else is on this breaker. Sometimes the breaker will trip. I have replaced the...

15 amp breaker [ 5 Answers ]

Rewiring my kitchen, I have refrigerator, stove with electronic ignition, exhaust hood, and a microwave, and a duplex plug. Wondering if too much power for 15 amp breaker. Thanks for any info.

Question on 12 gauge w/ 15 amp breaker [ 2 Answers ]

Hello, Glad to have found this place. Just had a question regarding 12 gauge wiring. While I know it is unsafe to use 15 gauge for a 20 amp breaker, are there any safety concerns using 12 gauge wire on a 15 amp circuit breaker? Reason I ask is I had recessed lights put in my basement and had...


View more questions Search