    I am installing 2 100 amp breaker boxes for a duplex from a double meter
    "i am installing 2 100 amp breaker boxes for a duplex from a double meter the one wire has to go through the basement of one side do I need a disconnect and I keep hearing I need to run a 4 wire to what will be called the sub panel after I put in the 100 amp disconnect
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Dec 10, 2010, 03:51 AM
    Yes, the cable that leaves a meter cannot go much more than ten feet inside the building without short circuit protection, so a disconnect is needed at the meter and from that point on 4 wire cable is needed.

    At this panel the neutral bar must be insulated and separate from the equipment grounds.
    char16101's Avatar
    char16101 Posts: 2, Reputation: 1
    New Member
     
    #3

    Dec 10, 2010, 04:34 AM
    Comment on tkrussell's post
    There is a bonding strip that came with the disconnect. I have wired houses before just never did a duplex.This whole 4 wire thing has got me just a little confused.Is there a diagram anywhere to see this
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #4

    Dec 10, 2010, 05:26 AM

    Are you an electrician?

    The issue is not between a single family home and a duplex.

    The issue is where the neutral gets bonded to the equipment ground.

    Only at the Main Service Disconnecting Means, or before, but never after this disconnect.

    After the MSDM, the neutral shall not be connected to any equipment ground.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Wiring 2 Gang Meter Socket w/ 100 & 200 Amp Meters [ 10 Answers ]

Hello, Are you allowed to use a 2 gang 200 amp meter socket to feed (1) 200 AMP panel and (1) 100 AMP panel, or do all meters in same enclosure have to be the same (200 AMP)? If the above is allowed: What size wire would I need from weather head to meter socket? Would I then run...

Can a 150 amp meter panal handel a 100 amp, 40 amp, 30 amp and 30 amp brakers. [ 2 Answers ]

My meter panal is a 150amp panal. I have a 60 amp sub panal coming off it a 30amp to my stove a 30 to dryer and a 40 to the a/c. i want to upgrade the 60 amp sub panal to a 100 amp panal. Will the 150 amp meter panal handel it or do i need to have a 200 amp meter panal installed

Adding a 200 amp breaker pannel to feed two 100 amp pannels [ 13 Answers ]

Hello all, This is my first post so I hope I do it right. This is what I got. The drop from the pole comes down to one 200 amp meter. The 200 amp meter feeds only one panel with a 100 amp input breaker and has many breakers that power the house (stove, water heater, dryer, outlets). Then it...

15 amp duplex recept on 20 amp circuit breaker [ 2 Answers ]

Can you put in 15 amp outlets that has 12 gauge wire on a 20 amp circuits these are just regular household outlets not used for dryers or refrigerator. Or should I replace with 20 amp outlets.

Running 2 100 amp breaker boxes on 200 amp meter base [ 1 Answers ]

I have 2 100 amp breaker boxes,but the meter base is 100 amp.Wanting to put 200 amp metet service with disconnect box.Can some one tell me if this is possible.and how you would connect the 2 breaker boxes to the disconnect box.Thank you


View more questions Search