    Is 200 amp transfer switch enough for two 200 amp panel
    Is 200 amp transfer switch is enough for two 200 amp panels to operate a 25ke generator.if the two panels are being inter connected.there is only one supply power from the single meter
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #2

    Jul 13, 2012, 06:36 AM
    It would be Easier? To Interlock one Panel, hopefully your necessary circuits are in 1 Panel.
    JOE956895's Avatar
    JOE956895 Posts: 2, Reputation: 1
    New Member
     
    #3

    Jul 13, 2012, 06:54 AM
    Quote Originally Posted by Stratmando View Post
    It would be Easier? to Interlock one Panel, hopefully your necessary circuits are in 1 Panel.
    Actually what I am doing is connecting one of the 200 amp panel to the other one and then connecting the transfer switch to that panel.is it against the code or is thereany danger?
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #4

    Jul 13, 2012, 07:13 AM
    Do Both 200 Amp Panels have separate disconnects/Main Breakers?
    Are you tieing both to the Main Lugs of 1?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #5

    Jul 13, 2012, 07:23 AM
    Sounds like two 200 amp panels served by a 400 or 320 amp meter.

    If this is the case, the ATS needs to be fully rated at 320 or 400 amp.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #6

    Jul 13, 2012, 01:09 PM
    Quote Originally Posted by tkrussell View Post
    Sounds like two 200 amp panels served by a 400 or 320 amp meter.

    If this is the case, the ATS needs to be fully rated at 320 or 400 amp.
    Exactly.

    You CANNOT "interconnect" the two panels.

    You can use the 200A transfer sw to feed ONE panel.
    Or you can use a 400A transfer sw to feed both panels

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Main Cutoffs: 200 amp outside panel feeding a 200 amp inside circuit breaker panel. [ 1 Answers ]

Would you please clarify an answer you gave to a previous question? Your answer makes me wonder about the capacity of the main shut-off circuit breaker in an inside circuit breaker panel. Is the inside circuit breaker panel the same as what you call a subpanel? Here's the question and answer:...

What size wire to a 200 amp panel 200 feet away [ 4 Answers ]

What size wire and how much for a 200amp box 200 feet away? I have a 200amp panel on a pole and want to run another box some 200 feet away to a man cave. It will house a fridge, lights, a window ac, and TV stereo. No heat as it will be wood burning stove. Gas oven and cooktop, one big 1200 sq ft...

200 amp main feeding 200 amp sub-panel [ 13 Answers ]

The utility spotter recommendeds the corner of my house as the location for a 200 amp aerial service entrance/meter base. My county requires a shut-off switch with the meter base, so a combination meterbase and load center is the standard here. I'm okay with her recommended SE location, but...

Extending 200 amp service to another 200 amp panel [ 1 Answers ]

Hello Everyone, As I just found this site this is my first time posting. I am in the process of doing an addition to my home and I am having the electrical service moved as the addition is on an exterior wall. I installed a new 200 amp panel and I need to extend the electrical over to my...


View more questions Search