    2 White Wires from GFCI single pole breaker
    Hello,

    I understand electricity quite well, but I have never seen this before. I am replacing a GFCI circuit breaker (15A), with a non GFCI breaker (15A), and am confused because there are 2 white wires (and the black), coming out of the bottom of this breaker. I know the newer breakers have a single GFCI, but why is there 2 wires?

    Should I just put these wires back onto the neutral bus bar?

    Thanks,

    Mark
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Jan 14, 2008, 09:50 AM
    One wire should be permenently attached to the breaker. There should be a silver Neutral lug near that wire for the load neutral from the circuit being protected. Is this second wire just cutoff? Can you find this screw terminal lug?
    MarkyD's Avatar
    MarkyD Posts: 2, Reputation: 1
    New Member
     
    #3

    Jan 14, 2008, 11:23 AM
    Quote Originally Posted by tkrussell
    One wire should be permenently attached to the breaker. There should be a silver Neutral lug near that wire for the load neutral from the circuit being protected. Is this second wire just cutoff? Can you find this screw terminal lug?

    Thanks for the reply. The box is pretty crowded. I haven't cut the power yet and delved into the wires too deeply to see where they are both going just yet. I wanted to have an idea of the plan before I went in.

    Mark

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Wiring Hot Tub and using a 50 Amp Double Pole GFCI Circiut Breaker [ 10 Answers ]

:confused: I keep getting the GFCI breaker tripping after wiring my hot tub. I wired 2 hot Red and Black to the proper terminals and the White to the neutral and the Bare Copper to the ground Post at the tub. I am using 6-3 w/G per instructions. Could the GFCI breaker be bad? When I wire...

How do I run all my wires to a single breaker [ 3 Answers ]

I am building a portable hunting cabin that will be used as a rv. It will be fully equipped with a 4.6 cubit foot refrigerator, a 5.9 freezer, a 2.5 gallon hot water water heater, and a 5000btu window a/c, 2 shop lights. It will have 4 outlets total, should I use a 30 or 50 amp breaker, and where...

Two Single Pole GFI's = one Double Pole 220v GFI? [ 6 Answers ]

Hello there, Installing a pool motor, 220v hayward northstar two speed. Could not find a double pole 40 amp GFI, electric supply store recommended two single pole 20A GFI's sharing a neutral? Does this make sense. I have a 40amp double pole in the main feeding the sub via the sub panel...

Double wires on a single wire breaker [ 3 Answers ]

Hi, My home inspector put the following in my inspection report and I would like to know if anyone know the possible solutions, including the lower cost ones. Also, does this create any danger or fire hazard? * the two improper double feeds in the sub panel in the Laundry where two...

Trying to change a single pole light switch to a single pole swith with a light below [ 5 Answers ]

I have a kitchen light and a basement light that are together in one electrical box, but are on single switches. I purchased a "single pole switch and pilot light" combination so I could see easily if the basement light is on. In the box there is a black, red and white wire. For the single pole...


View more questions Search