    100 amp service disconnect
    I have a 100 amp service disconnect and a 200 amp main box the 200amp breaker keeps triping but not the 100amp at the pole what could cause this it has been this way for 5 years now and just started doing this thanks
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Jan 10, 2010, 05:29 AM
    Since the 200 amp CB is tripping, and is downstream of the 100 Amp Main CB, overload is not the issue.

    There most likely is a loose connection at or near the 200 Amp CB. A loose connection will cause heat, the heat will be conducted through the metal into the CB causing the thermal device inside the CB to react, and trip.

    I once found a nut bolting the CB tab on the load side of a 200 amp breaker, with only a 20 (twenty) amp load, caused enough heat to trip the 200 Amp CB. I was only able to find this loose connection with an Infrared heat detector.

    Without having a detector handy, you may try tightening any and all connections. Ideally, the process is to loosen any connection, an then tighten to the proper torque specifications. Over-tightening can be as worse, and at times worse that a loose connection.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Service entrance cable size for 100 amp and 200 amp service. [ 16 Answers ]

I would like to know what size aluminum sec I would need for 100 or 200 amp service

400 amp service disconnect [ 1 Answers ]

I am installing a 400 amp service (non-residential). Outside of the building I want to put a Combination Service Entrance Device (meter main) with two 200 amp breakers. These breakers will feed two 42 circuit load centers located inside and directly behind the CSED. Do I need main breakers in each...

100 amp service vs. 200 amp service [ 4 Answers ]

:) I am looking at a small (totally remodeled home) with 100 amp service. I always thought it was better to have 200 amp. I will live there alone. Does this mean I can't run the dryer and microwave at the same time?

200 amp service disconnect [ 1 Answers ]

What type of 200 amp service disconnect ( type 3 ) is better, a fused type or breaker type? Are they both available with a knife switch type handle?

200 Amp Outside Service Disconnect [ 5 Answers ]

I NEED TO KNOW IF A "200 AMP OUTSIDE SERVICE DISCONNECT" IS THE SAME THING AS A "200 AMP OUTSIDE MAIN BREAKER OR LOAD CENTER"? SOMEONE PLEASE HELP ME!! HOME DEPOT WAS USELESS.:confused:


View more questions Search