    Header install
    I need to install a 6' french door in my basement outside wall for a walkout exit. Basement wall is 8" block. Wall is not weight bearing therefore the joist run parallel to the wall. How do I support the outside wall above the block to remove the bock and insert the header under the sill plate? I'm planning on taking out the top block on both sides to make a ledge to sit the header on. I need a little help.
    Thank you
    Tony
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #2

    Oct 5, 2014, 11:25 AM
    Screw 2X12 plates across the floor joists, then build a crib wall from 2X4's, fit it under the 2X12 plates making sure the crib wall is well supported on hard soil or flat block and tight against the plates. Do not set the header directly on the block, install 2X PW plate under it. I'd use a triple 2X6 since you won't have clearance for 2X8 unless you use 1X PT.
    tonys1228's Avatar
    tonys1228 Posts: 2, Reputation: 1
    New Member
     
    #3

    Oct 6, 2014, 11:08 AM
    I'm not sure I follow you. How to get support from the joist since the are running the same direction as the wall. Do you have a link I can look at?
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #4

    Oct 6, 2014, 01:32 PM


    The cross pieces tie the joists and they bear on the temporary wall. This is a picture of a long wall and you only need about 8 ft..
    Missouri Bound's Avatar
    Missouri Bound Posts: 1,532, Reputation: 94
    Ultra Member
     
    #5

    Oct 12, 2014, 07:33 PM
    First of all, and important to know is that ALL exterior basement walls are load bearing, regardless of the directon of the joists. Your brick wall is supporting the rim joist, which is supporting the wall above it You can cut the wall back at each side of the opening and install a lolly column to support the header. And you could use steel and reduce the thickness of the header.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

What size header do I need [ 4 Answers ]

What size header is needed for a 16 foot opening in an interior wall with trusses above. Wall currently separates kitchen and living room and I want to remove it. Living room is cathedral ceiling and kitchen is flat.

Window with no header [ 15 Answers ]

in what year was this allowed... http://img821.imageshack.us/img821/561/photoob.jpg http://img252.imageshack.us/img252/4229/photo1qx.jpg http://img293.imageshack.us/img293/5562/photo2ko.jpg the 2x4 at the top is noticeably bowing (not surprisingly) any thoughts about best way to remedy?

Wire through header [ 1 Answers ]

I'm trying to wire a light above a door that has a 2X6 header. The header has a gap between the 2 boards (there is no 1/2 inch plywood). Is it okay to run NM 12-2 wire through the gap in the header? Does this violate any codes?

Laminated header [ 3 Answers ]

What size laminated header would I need to use over an 18 foot garage door? And also a 12 foot door?

Header tank [ 1 Answers ]

HI, I have my hot water from my heating venting into my header tank but only when hot water and heating is on, if I put them on individual it does not happen?? Thermostat is OK and pump is fine.


View more questions Search