    Goodman blower time delay relay?
    There is a 6 minute delay from when my heat pump compressor comes on until the inside blower comes on. It used to only delay a few seconds. This is a Goodman A60-20 air handler. Do I need to replace the blower time delay relay?
    drtom4444's Avatar
    drtom4444 Posts: 3,282, Reputation: 145
    Ultra Member
     
    #2

    Dec 6, 2011, 05:38 AM
    I would just eliminate it. Just hook common and "G" directly to the fan relay and that will fix it. It should only be a few seconds, but basically it's a useless feature. Normally, the time delay is wired to run the fan a few minutes after the compressor turns off to get the chilled air out of the unit.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Goodman time delay fan relay problems [ 17 Answers ]

Hello, I have a goodman system and it freezes up when blower fan stops working. I have been told told it is the goodman time delay fan switch. Does this sound correct.. How much to fix and is it a diy project.. Thanks in advance.. :)

Goodman Air Handler Sequencer Time Delay? [ 11 Answers ]

I cannot find the part # for the time delay relay for the blower of my air handler (MOD #aepf3036163). Can anyone point me in the right direction? Thanks :) Courtney

Goodman PHK060-1 Indoor Blower Delay Problem [ 0 Answers ]

I have a Goodman PHK060-1 heat pump. Just recently I have been having a delay after the unit fires up. The outdoor blower starts, and the indoor blower starts anywhere from virtually instantly to five minutes later. Generally speaking, it *seems* like the longer since it has run (and possibly...

Goodman furnace power vent and indoor blower relay [ 1 Answers ]

Where are the power vent really and the indoor blower relays located in the Goodman GMP100-3 furnace. According to the repairman these needs to be replaced because the contacts may be bad

92 civic primary relay energizing delay [ 5 Answers ]

I am having problems with a primary relay on a 1992 honda civic. I have replaced the relay after the first round of diagnostics. I am still having a problem When the enterior of the car is hot you must open it up and let it cool before the relay will receive electricity and make its first "...


View more questions Search