    Wiring power transformer to furnace
    I have a lennox furnace & I am trying to replace my transformer. On my old transformer one side has a black wire coming out connecting to a black wire coming out of the furnace. On the same side there is a white wire connecting to a yellow wire on furnace. On the other side there is a red wire coming from transformer connecting to a yellow wire, a green wire coming from transformer connecting to a blue wire. On the new transformer from radio shack one side has 2 black wires and the other 2 yellow & 1 black. Where do I hook these wires up to? Help please...
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Jul 6, 2006, 03:39 PM
    Any chance of getting some pictures of these transformers and wires? Difficult to determine what the wires are for without more detail.

    Also need the new transformer part number. The two yellow and one black means the low voltage side may be two voltages, like 12 and 24 volts. Also need to be sure the VA rating of the new is the same or larger than the old one.
    mav_01's Avatar
    mav_01 Posts: 3, Reputation: 1
    New Member
     
    #3

    Jul 6, 2006, 09:15 PM
    Thanks for responding. I am going to attach some pictures of my old transformer. My new transformer is from Radio Shack and the part number is
    273-1512B.

    Name:  Picture 040.jpg
Views: 17428
Size:  34.8 KB

    Name:  Picture 041.jpg
Views: 10478
Size:  36.2 KB

    I have never changed this before so I am a little confused because I am not sure what the 2 yellow wire connect to, also I am not sure where I connect the 2 black wires to. I am assuming that the black wire between the yellow wires is the ground. I think I do not need the ground because the new one mounts to the furnace itself and that would ground it.

    Thanks for your help.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #4

    Jul 7, 2006, 04:25 PM
    Ok, on the new transformer the two blacks alone on one side are the 120 volt input, if there is a white line or tracer on one of these, it is the neutral and connects to the white input wire , and the other is black. If not then does not matter.

    The black with the two yellows may not be a ground, It may be called a center tap, which connects in the center of the secondary transformer coil, and supplies half of the voltage between the two yellows.

    Once you connect the line side, measure between each yellow and the center black to see what the voltage is. Even if no voltage, do not ground unless instructed to do so by the manufacturer.
    Between the two blacks should be 25 volts, which will connect to the blue and yellow from the furnace.

    This transformer at 25.2 volt and a max of 2 amps is 50 VA, which should be enough for a standard hvac system control power.

    Be sure to mount to clean metal for a good ground connection.
    mav_01's Avatar
    mav_01 Posts: 3, Reputation: 1
    New Member
     
    #5

    Jul 10, 2006, 09:15 AM
    Thanks for your help. My AC is finally working! Have a good one.

Not your question? Ask your question View similar questions

 

Add your answer here.


Check out some similar questions!

Power to furnace control board but stops there [ 3 Answers ]

Hi I was given a Nordyne KG6RA gas furnace. After installing, I turned on and there was a low hum when the power got to it. I held the door switch closed so I could see. After a few seconds there was a spark and then blue smoke and everything went dead. I could not see where the smoke came...

Connecting a power transformer to a light? [ 8 Answers ]

Hi, I have an outdoor lamp at my house that is/was using a power transformer for the lamp. First question: Why? The wires on one of the windings has been ripped off the unit and the base of the unit is very rusty. I do not know the manufacturer or the specs of the unit. So, I bought one,...

Wiring 12 volt transformer [ 1 Answers ]

I have recently installed some 12 volt miniature lights in home. I have them working now but began wondering about how I have the 12 volt transformer wired. The lights are on a switch and I have the transformer in the line before the switch. Thus I have power at the transformer all the time. Is...

Transformer wiring of tempstar furnace [ 2 Answers ]

Hi Labman, I had a bad relay (LY2 24 VAC), so I marked the wires on piece of paper to take it off and install the new one. The problem that I lost the paper somehow and I don't have a clue how to install the new one. I know that the I/p is 120 VAC and the o/P 24 VAC. How ever I have 6-wires...

Transformer wiring [ 18 Answers ]

I have a Payne furnace that had a Intermatic wall timer connected to it. The timer was causing the furnace to come on at various times and sometimes just the blower (it'll run all night). If I hit the on/off button on the timer, it'll disable it for 24 hours. I attempted to disable the timer...


View more questions Search