Ask Experts Questions for FREE Help !
Ask
    mannye's Avatar
    mannye Posts: 2, Reputation: 1
    New Member
     
    #1

    Dec 12, 2006, 10:21 AM
    Gas Valve pressure test
    I just ordered a new gas valve for my fireplace. I damaged my old one by blowing compressed air into it to remove spiders that had found their way in through the gas orifice to the burner.
    Question: how do I test the water column pressure on the new valve, or do I assume it already comes pre-set from the manufacturer?
    newaukumdon's Avatar
    newaukumdon Posts: 525, Reputation: 44
    Senior Member
     
    #2

    Dec 12, 2006, 09:12 PM
    The valve does not control pressure that would be done by the regulator at the gas meter or if propane, the regulator before the house. Should be 11 inches water column or 3-5 PSI to the valve.

    I am not a gas expert and would check to see regulator PSI
    Regards,
    Don
    NorthernHeat's Avatar
    NorthernHeat Posts: 1,455, Reputation: 132
    Ultra Member
     
    #3

    Dec 13, 2006, 05:22 AM
    There is a tap on the in and out of the gas valve. There is a pressure regulator inside it. You need a special gauge (magnahelic gauge) to adjust the output pressure. Most of the time they come preset pretty darn close to 3.5" W.C. This is pressure for Natural gas not LP is it?
    mannye's Avatar
    mannye Posts: 2, Reputation: 1
    New Member
     
    #4

    Dec 13, 2006, 06:27 AM
    Sorry, Newaukumdon, but I believe you are misinformed.

    From my reading on the subject, the water column pressure can be tested on the gas (natural, not propane) valve by way of 2 screws (A and B) located above the pilot control knob. The inlet should read 7", and the outlet about 3.5" .

    My question is if there is a specialized tool for this, or is there a an alternate way to check this pressure without the specialized tool/

    Also, would the new gas valve (ordered from the fireplace manufacturer) already come pre-set to those pressure readings?

    Perhaps a member in the HVAC trade would be able to respond to this.
    newaukumdon's Avatar
    newaukumdon Posts: 525, Reputation: 44
    Senior Member
     
    #5

    Dec 13, 2006, 05:11 PM
    We build a heating unit that uses a Robert Shaw control valve and even now I am looking and the only adjustment I see is for the pilot. But I am not an expert NORTHERNHEAT seems to have this one covered.

    Regards and good luck,
    Don
    PS The control units we get work great right out of the box
    caibuadday's Avatar
    caibuadday Posts: 460, Reputation: 10
    Full Member
     
    #6

    Dec 13, 2006, 06:19 PM
    Quote Originally Posted by mannye
    Sorry, Newaukumdon, but i believe you are misinformed.

    From my reading on the subject, the water column pressure can be tested on the gas (natural, not propane) valve by way of 2 screws (A and B) located above the pilot control knob. The inlet should read 7", and the outlet about 3.5" .

    My question is if there is a specialized tool for this, or is there a an alternate way to check this pressure without the specialized tool/

    Also, would the new gas valve (ordered from the fireplace manufacturer) already come pre-set to those pressure readings?

    Perhaps a member in the HVAC trade would be able to respond to this.
    What about a clear plastic tube (U shape, filled with water) connect to the valve , use 1/2 plastic fitting... the pressure of the gas would push the water in the U section up the vertical section of the tube( WC)... just an idea...

Not your question? Ask your question View similar questions

 

Add your answer here.


Check out some similar questions!

How to pressure-test gas pipe [ 15 Answers ]

Hi again! First, MANY thanks to you experts for the help I've gotten in the last month. I passed my plumbing inspection for my new bathroom and kitchen! Now, on to one more little one. I'm installing gas lines. The house was previously on oil heat and all other appliances were electric,...

Gas valve pressure problem [ 1 Answers ]

I had an old Coleman Evcon furnace, the problem is when the flame came out doesn't come strong because the fleame stay right at the nozzle of valve pipe,

Gas valve noise on main valve engagement [ 1 Answers ]

I have a carrier 58gs100ga furnace with a white rodgers 36e93 gas valve. The main gas valve solenoid chatters or rattles for a split second before it stays engaged after the pilot is proved. I just replace the spark/lock out board and the fan board for a different problem. This chatter is...


View more questions Search