    Furnace rheem 90 not igniting
    Rheem Imperial 90 Plus not igniting.

    Symptoms – When heat called for: tries to fire. Over and over a click from a module on the control board (ST788C1002). A green flash comes from the module on the control board that is clicking.

    Ignition Control Module – Honeywell 47-22481-01 – does not give any LED indications at all - No blinks at all on the LED on the Ignition Control module.

    Blower working fine.

    Sensor has been cleaned with sandpaper. Ignitor appears to be fine. It was replaced about 3 years ago. Heat Exchanger replaced about 10 years ago – warranty. Burners replaced about 5 years ago. I have photos taken today ready to forward if they will help.
  • Nov 18, 2011, 06:47 PM
    T-Top
    Sounds like to me you have a bad hot surface ignitor. If its not glowing and you can see a white ash spot on the ignitor its bad.
  • Dec 3, 2011, 04:50 PM
    KyJoey
    It's not the ignitor - I just replaced it with a new one, and same thing as described in original question.

    Any more ideas please?