    flash224's Avatar
    flash224 Posts: 5, Reputation: 1
    New Member
     
    #1

    Feb 23, 2012, 06:38 PM
    Furnace not responding to call for heat
    I have a comfortmaker furnace(model# GUG141A020IN) I have been working on this thing for 2 Days. Came home house cold, when I turn up thermostat "nothing", jumped it at furnace and it cycles up as normal. Now get this, if I turn up the temp and flip the switch from heat to OFF and flip it back to HEAT the thing fires up (sometimes) and runs as normal until it reaches the set temp, once it reaches the set temp it cycles off as normal. BUT when the temp drops below the hold temp, the thermostat calls for heat but the furnace does out respond until I go back through the afortmentioned routine. I've changed the control board and thermostat and still have the same problem. Furnace supply guy thinks it may be the relay(does anyone agree). I got a strong feeling that it is something simple that's KICKING MY BUTT... HELP and yes I know for the money I've spent I could've has it serviced.
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #2

    Feb 23, 2012, 07:33 PM
    You are resetting the control board fault any time you remove 24v from the W circuit. Its what we call a soft reset, its not a major fault but a fault that needs to be addressed. If you will count the blinks of the lights on the control board before you remove 24v or 115v it will give you the code to the fault.
    wmproop's Avatar
    wmproop Posts: 3,749, Reputation: 91
    Ultra Member
     
    #3

    Feb 23, 2012, 07:37 PM
    Quote: ( jumped it at furnace and it cycles up as normal. ),, jumpered it, what is it? Are you saying you jumpered tstat wires meaning bypassed the tstat?, if this is the case you also bypassed the tstat wires running from furnace to tstat, if this not the case, what did you jumpered?
    flash224's Avatar
    flash224 Posts: 5, Reputation: 1
    New Member
     
    #4

    Feb 23, 2012, 08:06 PM
    OK T-Top I'm quite the newby at this... what do you mean by remove 24v from the W circuit? I get that I need to count the blinks of the light on the control board but you lost me with "before you remove 24v or 115v". The lights seem to continuously flash to me during the cycle through. When should I be counting the blinks. And again please forgive me if I sound like a complete idiot lol.
    flash224's Avatar
    flash224 Posts: 5, Reputation: 1
    New Member
     
    #5

    Feb 23, 2012, 08:15 PM
    Yes I bypassed the tstat... "jumped" the R and W where they connect to furnace... and the furnace cycled through the start process as if It was starting normally from the tstat.
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #6

    Feb 23, 2012, 08:17 PM
    Any time you remove a thermostat or turn it off and then back on you reset the control board if it's a minor fault( by removing 24 volts from the heat call). You have to remove 115 volts from the system and then back on to reset a major fault.
    flash224's Avatar
    flash224 Posts: 5, Reputation: 1
    New Member
     
    #7

    Feb 24, 2012, 05:17 PM
    I have an older model furnace with an external low voltage damper above the furnace on the exhaust, apparently the damper was not communicating properly with the furnace. The damper has been set to always stay open and now the furnace seems to be working as advertised. If it starts back giving me problems I'll disconnect it from the furnace... I would have did it already but didn't want to take a chance of screwing something else up.
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #8

    Feb 24, 2012, 05:30 PM
    To be honest I don't know why you would have a vent damper on your 80% furnace any way.
    flash224's Avatar
    flash224 Posts: 5, Reputation: 1
    New Member
     
    #9

    Feb 24, 2012, 05:49 PM
    It was there when I brought the house!! Frankly didn't even know what the H*ll it was... live and learn

Not your question? Ask your question View similar questions

 

Add your answer here.


Check out some similar questions!

Rheem furnace fails to answer thermastat call for heat consistently. [ 1 Answers ]

My electric Rheem furnace fails to come on from time to time when thermostat calls for heat. If I trip and rest breakers on furnace, the furnace will operate normally for some time ( It will shut off and come back on per thermostat settings) but (Usually, in the evening) it will fail to come back...

I have two stage furnace the burners turn on off twice before the call for heat is co [ 1 Answers ]

I have a york 90%+ furnace it is two stage the burners cycle on and off twice before the call for heat is complete ,is that normal?

Intertherm furnace blower comes when it does not call for heat [ 2 Answers ]

The blower comes on when the furnace is not calling for heat

Goodman furnace response when call for heat but not led [ 1 Answers ]

TNH_BNA5809 I have a Goodman Furnace (Model # PGB 024075-1. The other day I called for heat, the system is not fire up, then I came out to the unit outside to unplug the connection between the Smart valve and the ignitor. It is fire up and run for awhile, and shut itself off. Please help. ...

Tempstar Furnace Malfunction Blows cold No Heat Call [ 23 Answers ]

Tempstar about 10 yrs old?? (was here when I moved in) (Model number: NUGS050AF01 Gas/Has pvc pipes extending to outside at side of house. Is a split system No heat call. If I turn thermostat to on and turn up thermostat, nothing will happen. If I turn the heat from auto to run, the...