    Bryant furnace?
    I have a bryant model 350mavo36080 series B input 80,000 output 74,000
    The furnace runs all day when it is cold but the house never gets above 60 degrees
    The temperature in the plenum is 84 degrees so the furnace is only raising the temp by 24 degrees
    All 3 burners are working
    The air being blown out of the registers in the house is not very warm

    The exhaust outside the house is 60 degrees so I am not losing the heat there
    It is a side instalation and the temp on the outside of the furnace, just above the place where the flames are is 156 degrees that is the surface temp on the outside of the furnace

    What can cause the plenum temp to be so low when all the burners are burning and no heat is lost ou the exhaust
    SeattlePioneer's Avatar
    SeattlePioneer Posts: 97, Reputation: 9
    Junior Member
     
    #2

    Jan 20, 2012, 05:08 PM
    Are the burners actually staying lit all the time, or are they cycling on and off?

    Do you have natural gas or propane and what are the weatheer conditions in your area--- typical for your area or extreme?
    edward65's Avatar
    edward65 Posts: 6, Reputation: 1
    New Member
     
    #3

    Jan 20, 2012, 05:28 PM
    On all the time
    Natural gas
    edward65's Avatar
    edward65 Posts: 6, Reputation: 1
    New Member
     
    #4

    Jan 20, 2012, 05:33 PM
    It has been below zero at night
    SeattlePioneer's Avatar
    SeattlePioneer Posts: 97, Reputation: 9
    Junior Member
     
    #5

    Jan 20, 2012, 05:45 PM
    You may have inadequate gas pressure being supplied by your gas utility due to high demand or other problems with the system ---- such as a frozen regulator or gas meter.

    Do you have ot5her gas appliances? If so, what types? Have you noticed any low flame conditions or problems with those other appliances?

    Around here, it's cold when it gets to thirty degrees!
    edward65's Avatar
    edward65 Posts: 6, Reputation: 1
    New Member
     
    #6

    Jan 20, 2012, 06:53 PM
    The range and water heater work just fine
    edward65's Avatar
    edward65 Posts: 6, Reputation: 1
    New Member
     
    #7

    Jan 20, 2012, 06:54 PM
    I can see good flames in there
    SeattlePioneer's Avatar
    SeattlePioneer Posts: 97, Reputation: 9
    Junior Member
     
    #8

    Jan 20, 2012, 07:05 PM
    <<What can cause the plenum temp to be so low when all the burners are burning and no heat is lost ou the exhaust
    >>


    That is a very good question --- and the answer is pretty much nothing.


    That implies that you have inadequate gas pressure to the furnace or perhaps a defect in the gas valve resulting in gas pressure to the burner manifold that is too low.


    So you need to have someone measure the gas pressure at the furnace, typically about 3.5" water column, and the burner manifold pressure.

    I have seen very rarely furnaces that had the wrong size burner orifices installed, so that should be checked at the same time.

    One furnace had burner orifices 'way too small installed at the factory. The homeowner had spent several years in a very cold house, and the heat exchanger was so cold the combustion gasses were condensing in the furnace and completely plugged the heat exchanger with rust.

    How old is the furnace and how long has this been a problem?
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #9

    Jan 20, 2012, 07:35 PM
    Have you checked to make sure your return air duct is not pulling in outside air?
    SeattlePioneer's Avatar
    SeattlePioneer Posts: 97, Reputation: 9
    Junior Member
     
    #10

    Jan 20, 2012, 07:49 PM
    Hmmmm. Good question T-Top! I suppose if you are sucking in enough of that zero degree outside air you aren't going to get much heat into the house!
    edward65's Avatar
    edward65 Posts: 6, Reputation: 1
    New Member
     
    #11

    Jan 20, 2012, 08:17 PM
    It has relatively short return ducts and long heat ducts, the return being in the middle of the house and the heat being on the outside walls

    Furnace is 1994 or 1995

    When I look at the flames in the burner box I see that at the top, some flame is not going into the tube for the flame and the burner box is hot on top so above that is where I get the 156 degree temperatur on the outside of the furnace. The furnace has not been working very good for a long time already and has been repaired by my furnace guy many times. Old parts are piled on top so I have a record of what was changed in parts. I plan on trying to clean the heat exchanger and run it with the exhaust pipe of for a while to see if it may be restricted. I already am taking combustion air into it directly at the furnace. The burner box has gotten hot enough to burn the plastic combustion intake pipe right through. The furnace can heat the house when the temp is above 10 degrees only. I am using some electric heaters and the temp will be up in the 30 degrees on Sunday. I am wondering if the heat exchanger could have something restricting the inside of it. What I really don't understand is where the heat is going because it isn't going out the exhaust and it isn't going into the heat ducts. The flames are there and it is very hot on the burner box so where is that heat going. It isn't out the exhaust tube because that is only 60 degrees.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Bryant furnace showing code 12-blower on after power up. Furnace won't start. Why? [ 0 Answers ]

Blower motor on all the time. No heat from furnace. Why?

Bryant furnace? [ 1 Answers ]

I have a Bryant furnace that works off a programmable thermostat. I'm having a problem now where the furnace will kick on as it is below the set temperature but before it reaches the set temp it will kick off and then right back on. It is like it is limiting out... what do I do?

Switch furnace to emergency mode on my Bryant 90 furnace [ 2 Answers ]

I have run out of propane and we are in the middel of a blizzard. How can I switch my furnace to emergency mode? Thanks, Brett

Bryant furnace [ 1 Answers ]

My furance fan will not shut off, I have taken off the t-stat and this does not help, the fan runs but the heat will not kick on any suggestions


View more questions Search