    ssport1's Avatar
    ssport1 Posts: 1, Reputation: 1
    New Member
     
    #1

    Jan 14, 2008, 03:16 PM
    Bleeding a baseboard hot water heating system
    I have a oil fired hot water boiler with baseboard heating. I have to replace the circulator and want to know how to bleed the system and then refill it when I am done. What is the proper procedure for this and what tools will I need?
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #2

    Jan 14, 2008, 04:38 PM
    Well, hopefully your baseboard has a coin vent or keyed vent at each room or drop into the floor(check under end covers)... here, simply fill the boiler and bleed through the vents until air is out of the system.

    If this is not the case then hopefully you will find a shutoff above and below (or shutoff flanges.. look close, actually on the side of the circulator flanges) the circulator you are going to replace (if this is case... super easy to fix, just shut shutoffs... replace circulator.. slightly tighten nuts/bolts and slowly open shutoffs to release any air from installation.. then tighten full on, then open valves... no need to bleed further!! )... IF you find the shutoffs as described you will probably also find a boiler drain above the circulator. Here, you would replace the circulator then you would keep the shutoffs shut and fill the boiler from the fill valve (most have a fast fill feature... a lever that allows quick fill... but be careful not to leave unattended.. can overfill/overpressurize and cause the boiler relief valve to go off) and then you would attach a hose to the boiler drain and purge the system of air (BUT only if you think you need to)... this takes some time... do not rush it... throttle up... throttle down until you can... say... take a full bucket of water and with the hose you are purging air with set into it... get little or no air when the hose is submerged for a minute or so! Then shut the water fill valve (P.S.I. on boiler should be at 12-15 P.S.I. maximum when finished), turn on the shutoffs and then turn on the boiler.

    Further, if there are vents and the boiler drain and shutoffs mentioned... use both to rid the system of all air!

    If there is not... well I recommend installing the setup described... just cut into pipe... install shutoffs above and below circulator (super easy replacement of circulator in the future.. so you won't have to go through this in the future) and install a boiler drain above the top of the circulator and follow instructions as presented!

    If I can help more just let me know... IF my answer was helpful, please RATE MY ANSWER below! Thank you!
    ggss321's Avatar
    ggss321 Posts: 1, Reputation: 1
    New Member
     
    #3

    Dec 9, 2010, 04:20 AM
    Excellent answer, very helpful.

Not your question? Ask your question View similar questions

 

Add your answer here.


Check out some similar questions!

Bleeding Hot Water Baseboard System [ 2 Answers ]

I have a gas fired boiler that heats water, uses 1 circulator pump to pump water to 2 zones (each with its own thermostat), using copper pipe to baseboards with fins. I am having difficulty bleeding the air out. One zone heats fine, the other not at all. I think there may be some kind of air...

Loud banging from baseboard hot water heating system [ 6 Answers ]

I have been living in a home for 10 years with baseboard hot water gas heating system that has since day one given me headaches with a loud banging when the system is running. I recently installed a Hydronic gas boiler and accompanying European style slim radiators to the home to provide more even...

Banging noise from baseboard heating system [ 2 Answers ]

I own a condo which I rent out to a young couple. There are 6-condos in each building with a boiler in the basement sending heat to each condo-unit upstairs. Each condo has baseboard heat and it's own thermostat. Every time the thermostat shuts the heat off, a very loud "bang" is heard. ...


View more questions Search