    Whould it be safe to run use an extension cord like the following?
    I want to run a heavy duty extension cord 100 ft. long from my condo to my neighbor's generator when we lose power. The cord must be strong enough for a vehicle to drive over it. At the other end I would plug into it the refrigerator, a fan, a light, at the most three items. Is this possible and what advice can you give me?
    Kyle_in_rure's Avatar
    Kyle_in_rure Posts: 341, Reputation: 10
    Full Member
     
    #2

    May 29, 2011, 12:37 PM
    Although it is not really recommended, yes, you can do that. I have two neighbors that do the same thing. Make sure you are using at least a 12 or 14 AWG heavy duty cord. A vehicle running over it could cause some scuff marks and maybe eventual wire damage, but if it's just for the duration of a simple power outage it shouldn't be a problem. However, if it comes to the point where individual wires are damaged inside the cord (bare copper showing) you will have to throw it away or remove the damaged part. Good luck.
    deborahb77's Avatar
    deborahb77 Posts: 2, Reputation: 1
    New Member
     
    #3

    May 29, 2011, 05:21 PM
    Comment on Kyle_in_rure's post
    Therefore, get a 200 ft. heavy duty extension courd to lay the cable outside the travel area and not have vehicles possibly run over it?
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #4

    May 29, 2011, 06:14 PM

    Just get two 8' 2x4's and lay them side by side with the cord in the middle. The car will run over the 2x4's and never touch the wire.
    Kyle_in_rure's Avatar
    Kyle_in_rure Posts: 341, Reputation: 10
    Full Member
     
    #5

    May 29, 2011, 06:40 PM
    No I just meant that the cord may wear out after while, not that you have to avoid the area entirely. I would use stanfortyman's Idea. That's actually a really good idea.
    hkstroud's Avatar
    hkstroud Posts: 11,929, Reputation: 899
    Home Improvement & Construction Expert
     
    #6

    May 29, 2011, 06:48 PM

    This sounds like a good plan. It might work and then again it might not

    .
    It might work
    IF the generator puts out the advertized 120 volts. Most of the time the portable emergency generators just barley do.

    IF the extension core is 12 gauge wire. The term "Heavy duty" means nothing.

    IF the distance is kept to 100 foot.

    IF the fan and light are not being used when the refrigerator starts up.

    We do not know the amperage draw of the refrigerator nor do we know the starting amperage.

    If we assume a 6 amp draw and an 8 amp starting amperage the estimated voltage drop for 100' of 12 gauge wire would be 3.1 volts. Giving 116.9 volts at compressor start up.

    The compressor might start at that voltage or it might not.

    What do you think Stan? Am I all wet here?
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #7

    May 29, 2011, 06:52 PM

    Personally, with a newer refer I think a 100' 12ga cord will be fine.
    Think about job sites with 100 footers all over the place and 15A circular saws running amuck.

    As long as it is a temporary situation!
    Kyle_in_rure's Avatar
    Kyle_in_rure Posts: 341, Reputation: 10
    Full Member
     
    #8

    May 30, 2011, 08:38 AM
    What wattage generator is your neighbor's? And do you know how much stuff they will be running? I've personally ran a fridge, 2 lights, and a fan all on one 100' 14 awg cord at the same time. Every situation is different, though, my fridge uses 2.5 amps running (I forgot the startup)

Not your question? Ask your question View similar questions

 

Add your answer here.


Check out some similar questions!

12 gauge extension cord 75 ft? [ 1 Answers ]

I am currently setting up my breaker box to be powered up in the event of a power loss to my home. I live "out in the sticks" and have been caught once with no power and watched as my basement was beginning to fill with water due to a intense rain storm that passed through the area. I found...

Can I use a 10/3 extension cord to run 220 apporximatley 100'ft? [ 2 Answers ]

I have a planer, an old Craftsman 12" from the mid 1930's to 1940's that is powered by a 208/230 volt 1 phase 5 hp 1725 rpm induction motor. I have this in my garage/utility building/shed/woodshop/workshop which does not have any power run to it. At the present moment, I am using a standard 100' ft...

Extension Cord? [ 5 Answers ]

I am wondering if a person can cut the ends off an extension and use it to run power from your house to a shed. The extgension cord is a heavy duty 10 gauge cord. And can you run it through conduit? There would be 20-25ft of this cord in conduit and 25ft ran in the house. I'm just looking to save...

In wall extension cord? [ 2 Answers ]

We had our TV mounted and installed a month ago and the installer said I should get an in wall extension cord because I couldn't run the tv's power cord through the wall. But when I googled the in wall extension cords it said that they weren't permanent fixes. What do I do to conceal the TV power...

Make uf extension cord [ 3 Answers ]

Since outdoor extension cords should not be buried, can you make a uf cable "extension" cord to plug into a ground fault outdoor outlet and then bury it?


View more questions Search