    30 amp buss fuse - TL vs W
    RE: electric clothes dryer fuse to replace

    What is the difference between these 30 amp buss fuses -- TL vs W?

    When should I use TL and when W?
  • Feb 16, 2008, 06:05 AM
    tkrussell
    The W series is a fast acting fuse, and the TL series is a Time Delay.


    Time delay is designed to allow the high inrush current from a motor starting to flow, and allow the motor to start. The inrush current reduces down to normal running current after a few cycles.

    A W offers more precise protection, if needed, by limiting current to a level closer to the fuse rating. Depending on the size motor, or other device with high inrush current, a W fuse may open if the inrush current is too great.


    For most purposes, including this dryer, the Time Delay fuse is recommended.