    3 wire breaker into 4 wire?
    I am changing the service drop from my house to my garage. I have a 200 amp panel in the garage with new meter and am running a 60 amp breaker to the 60 amp panel in the house. I am running 4 wires to the old breaker box in the house via underground. Currently the old, via 1953 Breaker box, is setup for a 3 wire feed, so neutral and ground are all in one "screw down block". Is there a new "ground" block I could purchase and install in the panel to separate the grounds and use my new 4th wire as the ground?

    Thanks, Lucas
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Dec 27, 2006, 04:00 AM
    You should be able to find a new "Neutral" bar or lug, which will be insulated by sitting in plastic mounting feet, and you can also find a new "Equipement Ground" bar, which will not be insulated and bolt directly to the panel's metal back box, at home centers or an electrical distributor.

    Since your spending all the money and time to upgrade, can you find the extra dollars to replace the 54 year old panel and breakers? You don't mention what size the new cable is, but you should be able to upgrade to a new 100 amp panel, depending on the size cable.

    The new panel will have the new Neutral bar, you will need to ask for the Equipment bar, as an addition to the new panel.

Not your question? Ask your question View similar questions

 

Add your answer here.


Check out some similar questions!

Neutral wire is hot(has voltage potential like the black wire) [ 5 Answers ]

Hi, The problem started at midnight last week. One of my line in the basement is starting to have issue whenever I connect a water pump or appliances to the outlets. Before I plug the appliance in, the neutral is neutral(zero voltage), but when I plug the appliance in, the neutral is now...

Wire size in a 100 amp breaker [ 1 Answers ]

I was wondering if a 2/0 wire will fit in a siemens 100 breaker? Thanks for your help

Outlets to breaker/wire ratio [ 2 Answers ]

How many 60 Watt light outlets can I run off one 15 Amp breaker, using 14/2 wire?

3-wire home, 3-wire fan, 2-wire remote [ 9 Answers ]

Greetings, My home is 3-wire. I bought a Hunter ceiling fan (model 23811). The fan came with a remote assy. That I do NOT want to use... The fan has standard 3-wire connections (black, white, blk&white strip, ground). The remote receiver home-side wiring looks to be for 2-wire (blk and white)....

Trying to wire new breaker [ 5 Answers ]

We are trying to wire a 60 amp breaker into a breaker box that has no other breakers in but does have power. The breaker is for a 12/3 220 wire for an a/c unit. We hooked up all wires but a/c is not getting power. We need to make sure that all wires are connected properly. Thanks


View more questions Search