    Calculation of short-circuit current in delta winding of tertiary winding transformer
    Good day all

    I have a three-winding power transformer with vector grouping of YNyd11. I also have the utility short-circuit currents at the primary and secondary wingdings, and the primary-secondary, primary-tertiary, and secondary-tertiary positive and zero sequence impedances. I must calculate the three-phase and single-line-to-ground (SLG) short-circuit currents at the tertiary (delta connected winding) of the transformer.

    Standard short-circuit analysis software (using ANSI C37.010) appear to ignore single-line-to-ground short-circuit current at the delta winding of a tertiary transformer. We however, need to calculate the prospective short-circuit current at this winding for protection co-ordination. Can you provide any guidance for how this can be done?

    I already calculated (manually, as well as software verified) the three-phase short-circuit current at the tertiary winding by constructing the equivalent circuit for the three-winding transformer (by finding ZP, ZS and ZT) [ABB Electrical Transmission and Distribution Reference Book, fifth edition, pg 136] but have not found a way to calculate the SLG for the tertiary winding.

    I am thinking this should be easy, since the purpose of a delta-connected tertiary is specifically for unbalanced faults (SLG), but I am not finding any calculation dealing with it anywhere. I am only finding the example to calculate the three-phase fault on the tertiary, which uses only the positive sequence impedances.

    This was a very useful page > http://yourelectrichome.blogspot.com/2011/08/three-winding-transformers.html

    Any assistance is much appreciated.

Check out some similar questions!

How to calculate the short time current rating for current transformer? [ 4 Answers ]

Respected sir's, Please clear my doubts? How to calculate the "short time current rating"(i.e-primary short time current rating-like if u take 400-400/5-15va/class1,40ka/3sec). 40ka/3sec-how to calculate this rating from the substation? Is there any formula?please advise me... ...

How grounding of tertiary winding of Power Transformer helps in reducing the harmonic [ 7 Answers ]

If we use the tertiary winding of a Power Transformer as an Open Delta and ground it then how could that will be helpful in reducing the harmonics of system?

Short circuit current calculation in dc system [ 0 Answers ]

How do we calculate short circuit current in dc system?

Conversion of voluntary winding up into compulsory winding up [ 1 Answers ]

Can a voluntary winding up be converted into compulsory winding up by court during winding up process

Current transformer - short time withstand current [ 4 Answers ]

Hi, For ring-type (window-type) CT, do we need to size the CT short time withstand current at the same or above the system short time withstand current (short circuit level)? Any reference/technical explanation? Thanks!


View more questions Search
 

Add your answer here.