Have just fitted a SanifloPlus downstairs, nowhere near a vent pipe. We have a cesspool in the yard, and have plumbed the new sink and toilet into the waste pipe outside - but blocked the vent on the tank because of the lack of venting. Do I have to run a separate pipe through the wall and up to the roof? We live in the tropics, so no freezing worries.
Thanks for advice!
Milo Dolezal
Jan 23, 2017, 10:36 AM
Cut 'n' Paste from installation instructions ...
".....As per plumbing code all P-traps need to be vented. Therefore, even though macerating systems are isolated from the main drain system (by means of a check valve), the trap of the hand basin, shower, bathtub or bidet must be vented. The following external macerating systems MUST be vented: Saniplus, Sanipack, Sanibest and Sanigrind. Systems with built-in motors, such as Sanicompact and Sanistar need not to be vented (they are considered to be a forced main)...."
Hope that helped
Milo