Hot water heater does not have a pipe on the pressure relief valve and I need to add one. Can I run it down into the pan? Is that to code? Thanks.
ma0641
Mar 21, 2014, 04:55 PM
Code today requires it be vented outside but I see a number of older units that are pointed down to the pan.
macplumb
Mar 21, 2014, 05:40 PM
In Michigan I have done this and passed inspections many times.
massplumber2008
Mar 22, 2014, 06:08 AM
Yeah, as always, codes differ by state, but in most cases, stopping the T&P relief valve pipe about 6" above the water heater pan is acceptable. Installing an AUTOMATIC WATER HEATER SHUT OFF VALVE with a sensor in the pan would be something to consider if this water heater is in a finished basement.
Mark