Two days ago my plumber moved my thermostat to a new position in our lower level (in-floor radiant). 36 hours later the temp had dropped 10 degrees. When looking at the zone valve (honeywell v8043e1012) the motor (a replacement) was very hot and when I pulled it off it keep running as long as the thermostat was above the room temp. I then checked the other five valves and one motor was even hotter than the first. I disconnected that motor and it also keep running until I disconnected the yellow wire.
My question is are these motors supposed to keep running or do they open the valve then stop? Are these two motors wired incorrectly?
My question is are these motors supposed to keep running or do they open the valve then stop? Are these two motors wired incorrectly?