JAnderson1
Oct 15, 2011, 10:39 AM
I installed a tile backsplash in my kitchen in August and I needed to add outlet box extenders to accommodate the extra tile width. I was checking the voltage on the end of the line plug in the three outlet circuit with a tester and I touched a black wire to the side of the box and it sparked and popped the breaker. Since that time I have no voltage in the plug itself but I have 120 V at the black wires when I touch the other meter probe to the ground or the outlet frame or center screw. Obviously I would like to get the voltage back. I replaced all three outlets and it I have the same condition in all three outlets. It is possible that I burned something off in the breaker in the service box? Or did I burn a white wire in the wall somewhere where I can't see it? When I touch a probe to the black wires and the other probe to a white wire, I get 0 volts. I am not sure where to go next? I know my meter will test continuity but I have never done that - my only idea was to check continuity on the whites between boxes to try to isolate a break. Any advice would be great?