A 12/3 homerun supplies circuits R21 and R22. These 2 circuits supply a storefront. R21 supplies 3 receptacles controlled by a switch. R22 also supplies 3 receptacles controlled by a switch. They only supply the receptacles shown. 600.5(A) states "Outlets must be supplied by a branch circuit rated 20 amps or more and that supplies no other load."
1. Is there any code issue with sharing a neutral to supply these 2 storefront circuits?
2. Are there any other flaws in this storefront plan?