jimssr
Dec 7, 2010, 10:11 AM
Topic: None Chosen
Your Question: "i have a coleman furnace model dgat056bdd i have replaced the ignitor and the sensor rod the combustion blower is ok the centrifugal is ok and the blower is ok too but this is what it is doing for heat it turns on the combustion blower turns on for about 30 sec. then the ignitor turns on for about 15 sec. then the gas turn on it burns for about 60 sec. then the blower turn on but when it does the gas turns off now the blower stays on the combustion blower stays on to after about two min. the gas turns back on for about 60 sec. and turns off it will do this 4 to 5 times then the furnaces turns off but the control board light is only blinking one time . now if i turn it off then it will run again just like it did before if anyone knows what is wrong i would be very thankfull for your help"
Your Question: "i have a coleman furnace model dgat056bdd i have replaced the ignitor and the sensor rod the combustion blower is ok the centrifugal is ok and the blower is ok too but this is what it is doing for heat it turns on the combustion blower turns on for about 30 sec. then the ignitor turns on for about 15 sec. then the gas turn on it burns for about 60 sec. then the blower turn on but when it does the gas turns off now the blower stays on the combustion blower stays on to after about two min. the gas turns back on for about 60 sec. and turns off it will do this 4 to 5 times then the furnaces turns off but the control board light is only blinking one time . now if i turn it off then it will run again just like it did before if anyone knows what is wrong i would be very thankfull for your help"