View Full Version : My janitrol furnace is not responding


donryan00
Oct 10, 2008, 10:05 AM
Furnace - Janitrol GMP100-3 (circa 2000)

I can turn on the air conditioner and the fan, but the furnace isn't working at all. There are no pilots lit. It's like it has no power, but when I remove the panel and check the wires, I can get the red LED light to come that indicates whether the front panel is on or not. Help!

donryan00
Oct 10, 2008, 10:10 AM
By the way, I reset the breaker, switched the inside power switch and external switch on and off. Nothing. I have a Honeywell digital thermostat, but it all worked last winter.

donryan00
Oct 10, 2008, 11:01 AM
It was as simple as checking the battery contacts at the thermostat. Works fine now.