Can I run phone line in the same stud holes that the eletricial was run in
KISS
Aug 8, 2008, 05:07 PM
Recommended parallel spacing is 6". Besides, you don't want hum in your phone. OK to cross perpendicular.
benaround
Aug 8, 2008, 10:59 PM
Can I run phone line in the same stud holes that the eletricial was run in
Did you drill the holes or did the Electrician ? A lot of Electricians are not keen on drilling
Holes for other people, plus, as KISS said being that close can induce a hum in the phone.
Washington1
Aug 9, 2008, 09:29 AM
I usually try to keep my LV wire 6-12 inches away, yet at times I may have to run the LV with HV--yet it's normally one hole.
Note: Today's low voltage wire has improved.