Jun 28, 2008, 11:22 PM
Hi Experts,
I have an old mechanical thermostatT834C - I'm trying to replace with a programmable Honeywell RTH111.
I have only 3 wires: R (Red), Y(Yellow), W(Green) - in my old thermostat.
I have connected Rh,Rc(Red), Y(Yellow), W(Green) - in new thermostat.
The Rh, Rc are jumpered. There is a HG setting for the fan, I have left as is.
When I turn on the system to A/C, the cooler seems to work, but I don't think the fan really works. The temperature does not cool and I see very little air coming from the vents.
How can I fix this, is it because there is no wire for the 'G' terminal?
I;ve tried both 'Auto' and 'On' modes, no luck.
Please help!
Vic