Andy123
Jan 5, 2008, 08:12 PM
Not sure what is going on - need an advice:
40 year old house with incoming water pressure regulator.
Pressure with water running about 50 PSI, with faucets closed 60 PSI.
When I had no expansion tank with all faucets closed pressure was slowly going to about 100 PSI while water heater was heating water.
So today I installed expansion tank, set tank air pressure at 50 PSI before installation.
Now I see that pressure going to 120 PSI+ within an hour.
I have WATTS gage permanently installed right next to the tank so I can monitor pressue.
I know expansion tank is working because if I open faucet I see no water meter movements for 10-15 seconds until it empties the tank.
So question - what I did wrong?
Tank too small?
I can get a large one tomorrow, but want to get an advice first.
Thanks