I am installing black pipe for a gas heater in my garage. At this point everything is roughed in, no installation on sheetrock. Because of the way it is build I would like to install black pipe across the back of the garage approximately 40 ft. How do I get 10 foot sections into the wall studs that are 16 in centers.
Thank you
John harmon
sonettraining
speedball1
Dec 4, 2007, 07:23 AM
You notch the studs to accommodate the pipe and cover the notches with nail plates. Good luck, Tom
iamgrowler
Dec 4, 2007, 07:55 AM
I am installing black pipe for a gas heater in my garage. At this point everything is roughed in, no installation on sheetrock. Because of the way it is build I would like to install black pipe across the back of the garage approximately 40 ft. How do I get 10 foot sections into the wall studs that are 16 in centers.
When feasible (meaning no siding or Tyvek house wrap has been installed yet), I drill a hole through the side of the house or garage and feed the line through from the outside.
If it isn't feasible, I generally opt for a ductile gas piping material like Trac-Pipe or Gas-Tight.