Sep 2, 2007, 02:32 AM
I have had a loft conversion built with onsuit bathroom the council said I have to have air test on pipe work

cerbhunt
Sep 2, 2007, 04:54 AM
i have had a loft convertion built with onsuit bathroom the council said i have to have air test on pipe work

This is probably because you had a water tank in your loft that you have now removed, it is therefore likely that you have converted to a pressurised water system (you're probably getting the best showers you've ever had in the house). As your plumbing system was designed to supply water from a gravity system (ie from you old tank) the council want to make sure that this system can withstand the, much greater, pressures delivered by the mains water system

speedball1
Sep 2, 2007, 06:09 AM
i have had a loft convertion built with onsuit bathroom the council said i have to have air test on pipe work
In a air pressure test the water system's capped off and air is injected into the closed system. In my area it's 125 PSI for 8 hours. If the system holds you're good to go. If not then repairs are in order. Good luck, Tom