Water pump will not shut off

Asked Sep 30, 2008, 06:02 PM — 12 Answers
My water pump will not shut off. The other day my water run out so I had to prime the pump. I got water back but now it won't shut off on it's own. I can manually shut it off from the pressure switch. I noticed the pressure gauge will reach a certain point to turn on but then seems stuck there. It won't raise or lower. I got good water pressure. I already know my well needs to be dug deeper because the water table in the area has dropped. Any suggestions would be greatly appreciated. Thank you

12 Answers
speedball1's Avatar
speedball1 Posts: 27,655, Reputation: 9541
Senior Plumbing Expert
 
#2

Oct 1, 2008, 02:14 PM


Will it pump up to the cut-off PSI? Regards, Tom
Helpful
ddchristian's Avatar
ddchristian Posts: 5, Reputation: 1
New Member
 
#3

Oct 1, 2008, 04:00 PM
The pressure gauge will go up to about 32 and no higher. I have tried to adjust the points to lower pressure and that didn't work so I tried higher and that didn't to anything either. The bottom valve, not sure what is called, is leaking really bad now. A nut that was on it broke in two when I opened the valve.
Helpful
mygirlsdad77's Avatar
mygirlsdad77 Posts: 5,539, Reputation: 1650
Plumbing Expert
 
#4

Oct 1, 2008, 04:26 PM


If your pressure seems to be good at the faucets(better than 32psi) then I would start by replacing your pressure gauge. If you get a more accurate reading, your pressure switch may be bad. If replacing these components doesn't help, you may have some serious problem(bad, or plugged pump, leak undergroud.
What kind of pressure did your gage show before you had this problem? Should have been between 40 and 60 psi.
You mentioned a low water table. Are you sure your pump isn't running dry. Go to the well, take off the well cap and listen. Tell me what you hear.
Thats all I have for now. Let me know what you find.
Good luck
Helpful
jlisenbe's Avatar
jlisenbe Posts: 2,356, Reputation: 617
Well & Pump Expert
 
#5

Oct 1, 2008, 05:14 PM
DD, could it be that the valve (I assume the main shut-off valve) is leaking so badly that the pump cannot deliver sufficient volume to get above 32#?
Helpful
ddchristian's Avatar
ddchristian Posts: 5, Reputation: 1
New Member
 
#6

Oct 2, 2008, 02:13 AM
I believe that could be one of the problems because now I don't have water this morning. Does anyone know if I can just replace the nut that broke or do I have to replace all of it?
Helpful
speedball1's Avatar
speedball1 Posts: 27,655, Reputation: 9541
Senior Plumbing Expert
 
#7

Oct 2, 2008, 04:59 AM


If you're referring to the bonnet packing nut, if you have a old valve around that uses the same size I would say your only option would be to replace the valve. However, in my opinion, you have more problems then just a leaky shut off v alve. But first things first. Repair or replace the valve and get back to us with the results. Good luck, Tom
Helpful
mygirlsdad77's Avatar
mygirlsdad77 Posts: 5,539, Reputation: 1650
Plumbing Expert
 
#8

Oct 2, 2008, 04:46 PM
How badly is the valve leaking? I doubt that this leaky valve would cause you to have no water. But you just as well replace the valve first( going to have to do it anyway). Still curious about your water table.
Helpful
ddchristian's Avatar
ddchristian Posts: 5, Reputation: 1
New Member
 
#9

Oct 2, 2008, 06:48 PM
Ok, got it working now. I replaced the shut off valve and the pressure gauge. It seemed to be the pressure gauge that was causing the problem. Thank everyone for helping me out with this.
Helpful
jlisenbe's Avatar
jlisenbe Posts: 2,356, Reputation: 617
Well & Pump Expert
 
#10

Oct 2, 2008, 06:59 PM
Of all the things that might have been causing the problem, the pressure gauge was not it. All it does is read pressure, not regulate it. It probably was, of course, defective.
Helpful

Not your question? Ask your question View similar questions

 
Thread Tools Search this Thread
Search this Thread:

Advanced Search

Add your answer here.

Remove Text Formatting

Undo
Redo
 
Decrease Size
Increase Size
Bold
Italic
Underline
Align Left
Align Center
Align Right
Ordered List
Unordered List
Decrease Indent
Increase Indent
Insert Email Link
Wrap [QUOTE] tags around selected text
Wrap [CODE] tags around selected text
Wrap [HTML] tags around selected text
Wrap [PHP] tags around selected text
Wrap [YOUTUBE] tags around selected text
Notification Type:



Check out some similar questions!

The ac pump will not shut off [ 1 Answers ]

Hello, the pump located beside the gas heater comes on and off with the ac also but it won't shut off. What could cause this?

My heat pump won't shut off on its own! [ 4 Answers ]

I have a 2 ton Payne heat pump that is truly living up to its name "Pain". It's performance is very inconsistant. 99% of the time, the heater runs constantly. It won't go into on/off cycles on its on. 1% of the time it will remember how to work correctly, and may cycle on and off a few times. ...

Heat Pump Mystery- fan won't shut off, even w/ new board. [ 1 Answers ]

No matter what, I can't get blower fan to shut off. I set thermostat fan switch to off- it still runs; I set thermostat system to off, it still runs. I changed the control board- no effect. I can find no limit switch. Anyone know what it might be? It's a Bryant H.Pump.

Well pump won't shut off [ 2 Answers ]

Jet pump won't shut-off. I just preplaced the pressure switch because it was leaking and now the pump builds to about 20lb and the pressure gage starts to bounce around. When the pump is unpluged the pressure in the pressure tank drops to 0. Pressure tank is 4 years old (air at 23 psi). I tried...

Heat Pump will not shut off [ 53 Answers ]

I have a Bryant heat pump that was used very little over the winter. When I went to turn on the air conditioning a few days ago, the outdoor unit would not come on, but the indoor fan and thermostat appeared to be working fine. I checked the contactor and it was not pulling in, when I pushed it...


View more Plumbing questions Search